Coolant concentration
ABB recommends diluting coolant 50:50 with water. Note that the concentration of coolant
should not be less than 33% and not more than 60%. Following table shows how the diluting
portion effects to frost protection.
Water concentration
Coolant concentration
Frost protection down to
66%
33%
-20 °C (-4 °F)
60%
40%
-27 °C (-16.6 °F)
50%
50%
-38 °C (-36.4 °F)
40%
60%
-54 °C (-65.2 °F)
WARNING!
Operation at liquid temperatures below 0 °C (32 °F) is not permitted even with
antifreeze.
Coolant mixture quality
The pH level of the coolant
must not
be manipulated by adding chemicals not specified in
this document. This may build up sediment in the liquid.
Approved coolants
•
BASF Glysantin G30® or Valvoline Zerex G30®.
For other coolants, contact your local ABB representative.
WARNING!
Do not mix different approved coolants in any conditions! Replace the cooling
liquid always with same cooling liquid! Mixing different coolant types is a risk for
cooling system corrosion.
■
Materials
Materials used in the internal cooling circuit are:
•
stainless steel AISI 316L (UNS 31603)
•
heavy gauge aluminum
•
plastic materials such as PA, PEX and PTFE
Note:
PVC hoses are not suitable for use with antifreeze.
•
rubber gasket NBR (nitrile rubber).
Use only these materials in the external cooling circuit, too.
WARNING!
When connecting external piping to the internal cooling circuit, use only materials
that are specified above. Copper and brass must not be used under any
circumstances. Even minor dissolution of copper can cause copper precipitation
on aluminum and subsequent galvanic corrosion. The liquid cooling system may
not contain any zinc (for example, galvanized pipes) at all since zinc would react
with the inhibitor.
Cooling and heating 123
Содержание ACS880-77CC
Страница 1: ...ABB WIND TURBINE CONVERTERS ACS880 77CC wind turbine converters Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 10: ...10...
Страница 17: ...5 1 3 4 6 8 7 2 Safety instructions 17...
Страница 22: ...22...
Страница 40: ...40...
Страница 60: ...60...
Страница 73: ...2a 3b 4c 5 Air flow direction is towards the converter module Maintenance 73...
Страница 104: ...104...
Страница 108: ...Description CAN bus connection XCAN XCAN 108 BCU x5 control unit...
Страница 112: ...112 Dimension drawings...
Страница 113: ...Dimension drawings 113...
Страница 114: ...114 Dimension drawings...
Страница 126: ...126...