Notes:
1)
Default use of the signal in the control program. The use can be changed by a parameter.
See also the delivery-specific circuit diagrams.
2)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [0(2)…10 V,
R
in
> 200 kohm] input
selected by switch AI1. Change of setting requires reboot of control unit.
3)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [0(2)…10 V,
R
in
> 200 kohm] input
selected by switch AI2. Change of setting requires reboot of control unit.
4)
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by
DIO1 and DIO2.
5)
Determines whether DICOM is separated from DIOGND (ie, common reference for digital
inputs floats).
DICOM=DIOGND
ON: DICOM connected to DIOGND. OFF: DICOM and DIOGND separate.
6)
This input only acts as a true Safe torque off input in inverter control units. In other
applications (such as a supply or brake unit), de-energizing the IN1 and/or IN2 terminal will
stop the unit but not constitute a true safety function.
External power supply for the control unit (XPOW)
The control unit is powered from a 24 V DC, 2 A supply through terminal block XPOW. With
a type BCU control unit, a second supply can be connected to the same terminal block for
redundancy.
The XD2D connector
The XD2D connector provides an RS-485 connection that can be used for
•
basic master/follower communication with one master drive and multiple followers,
•
fieldbus control through the embedded fieldbus interface (EFB), or
•
drive-to-drive (D2D) communication implemented by application programming.
See the firmware manual of the drive for the related parameter settings.
Enable bus termination on the units at the ends of the drive-to-drive link. Disable bus
termination on the intermediate units.
Use shielded twisted-pair cable with a twisted pair for data and a wire or another pair for
signal ground (nominal impedance 100 to 165 ohm, for example Belden 9842) for the wiring.
For best immunity, ABB recommends high quality cable. Keep the cable as short as possible.
Avoid unnecessary loops and parallel runs near power cables such as motor cables.
The following diagram shows the wiring between control units.
BCU-x2
Control units of the drive 49
Содержание ACS880-607 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 607 3 phase brake units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 30: ...30 ...
Страница 32: ...32 ...
Страница 36: ...36 ...
Страница 44: ...44 ...
Страница 54: ...54 ...
Страница 62: ...62 ...
Страница 66: ...66 Maintenance ...
Страница 82: ...Dimension drawing bottom exit 82 Dimension drawings ...
Страница 83: ...Dimension drawings 83 ...
Страница 84: ...Dimension drawing top exit 84 Dimension drawings ...
Страница 85: ... Dimension drawings 85 ...
Страница 86: ......