The resistance (R) of the brake resistor assembly must be equal to or above the value
specified. Never use resistance values below the specified value.
•
The resistor must withstand the specified brake cycles.
•
The ventilation of the space/room in which the resistors are located must meet the air
flow amounts specified.
•
The resistor assembly must be equipped with a thermal switch.
WARNING!
IEC 60664 and IEC 61800-5-1 require double or reinforced insulation between,
resistor live parts and the sensor. If the assembly does not fulfill the requirement,
the I/O terminals on the control unit must be protected against contact and must
not be connected to other equipment, or the temperature sensor must be isolated
from the I/O terminals, for example, with a suitable relay.
Selecting and routing the brake resistor cables
■
Typical resistor cable sizes
See the technical data.
■
Minimizing electromagnetic interference
Obey these rules in order to minimize the electromagnetic interference caused by rapid
current changes in the resistor cables:
•
Shield the braking power line completely, either by using shielded cable or a metallic
enclosure. Unshielded single-core cable can only be used if it is routed inside a cabinet
that efficiently suppresses radiated emissions.
•
Install the cables away from other cable routes.
•
Avoid long parallel runs with other cables. The minimum parallel cabling separation
distance should be 0.3 meters (1 ft).
•
Cross the other cables at right angles.
•
Keep the cable as short as possible in order to minimize the radiated emissions and
stress on chopper IGBTs. The longer the cable, the higher the radiated emissions,
inductive load and voltage peaks over the IGBT semiconductors of the brake chopper.
■
Maximum cable length
See the technical data.
Placing the brake resistors
Install the resistors outside the drive in a place where they will cool.
Arrange the cooling of the resistor in a way that:
•
no danger of overheating is caused to the resistor or nearby materials
•
the temperature of the room the resistor is located in does not exceed the allowed
maximum.
Supply the resistor with cooling air or coolant according to the resistor manufacturer’s
instructions.
34 Guidelines for planning the electrical installation
Содержание ACS880-607 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 607 3 phase brake units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 30: ...30 ...
Страница 32: ...32 ...
Страница 36: ...36 ...
Страница 44: ...44 ...
Страница 54: ...54 ...
Страница 62: ...62 ...
Страница 66: ...66 Maintenance ...
Страница 82: ...Dimension drawing bottom exit 82 Dimension drawings ...
Страница 83: ...Dimension drawings 83 ...
Страница 84: ...Dimension drawing top exit 84 Dimension drawings ...
Страница 85: ... Dimension drawings 85 ...
Страница 86: ......