Routing the cables
■
General guidelines, IEC
•
Route the motor cable away from other cables. Motor cables of several drives can be
run in parallel installed next to each other.
•
Install the motor cable, input power cable and control cables on separate trays.
•
Avoid long parallel runs of motor cables with other cables in order to decrease
electromagnetic interference caused by the rapid changes in the drive output voltage.
•
Where control cables must cross power cables, make sure they are arranged at an
angle as near to 90 degrees as possible.
•
Do not run extra cables through the drive.
•
Make sure that the cable trays have good electrical bonding to each other and to the
grounding electrodes. Aluminum tray systems can be used to improve local equalizing
of potential.
This figure illustrates the cable routing guidelines with an example drive.
min. 200 mm (8 in)
90°
*min. 500 mm (20 in)
1
2
3
3
2
1
4
min. 300 mm (12 in)
2
4
3
min. 300 mm (12 in)
*
Motor cable
1
Input power cable
2
Control cable
3
Brake resistor or chopper cable (if any)
4
■
Continuous motor cable shield or enclosure for equipment on the
motor cable
To minimize the emission level when safety switches, contactors, connection boxes or
similar equipment are installed on the motor cable between the drive and the motor:
•
Install the equipment in a metal enclosure.
•
Use either a symmetrical shielded cable (preferred alternative), or install the cabling in
a metal conduit.
•
Make sure that there is a good and continuous galvanic connection in the shield/conduit
between drive and motor.
•
Connect the shield/conduit to the protective ground terminal of the drive and the motor.
Guidelines for planning the electrical installation 67
Содержание ACS880-37LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 78: ...78 ...
Страница 116: ...116 ...
Страница 134: ...5 Set the real time clock 134 Maintenance ...
Страница 144: ...144 ...
Страница 167: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 167 ...
Страница 169: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 169 ...
Страница 170: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 170 Dimensions ...
Страница 171: ...Cabinet height and depth Marine construction option C121 IP42 side view Non marine IP42 side view Dimensions 171 ...
Страница 172: ...Location and size of input terminals Contact ABB for details 172 Dimensions ...
Страница 174: ...Inverter module cubicle with two R8i modules bottom cable exit 174 Dimensions ...
Страница 175: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 175 ...
Страница 176: ...Brake chopper cubicle D150 176 Dimensions ...
Страница 177: ... Units with common motor terminal cubicle H359 Cubicle width 300 mm bottom cable exit Dimensions 177 ...
Страница 178: ...Cubicle width 300 mm top cable exit 178 Dimensions ...
Страница 179: ...Cubicle width 400 mm bottom cable exit Dimensions 179 ...
Страница 180: ...Cubicle width 400 mm top cable exit 180 Dimensions ...
Страница 181: ...Cubicle width 600 mm bottom cable exit Dimensions 181 ...
Страница 182: ...Cubicle width 600 mm top cable exit 182 Dimensions ...
Страница 198: ...198 ...
Страница 200: ...200 ...