Start-up
Contents of this chapter
This chapter contains start-up instructions of the diode supply unit.
The underlined tasks are necessary only for certain cases. The symbols in brackets, for
example [Q1], refer to the item designations used in the circuit diagrams. If a task is valid
only for a certain option device or feature, the option code is given in brackets, for example,
(F259).
Note:
The instructions do not cover all possible supply unit configurations. Always refer to
the delivery-specific circuit diagrams when proceeding with the start-up. This default start-up
procedure is valid for a supply unit equipped with a main breaker ([Q1], F255) and
an external auxiliary voltage supply (G307).
Note:
For the functional safety options, the start-up instructions are given in separate option
manuals. Reserve the necessary option manuals at hand before the supply unit start-up.
Obey their start-up instructions.
WARNING!
Obey the safety instructions during the start-up procedure. See
ACS880
liquid-cooled multidrive cabinets and modules safety instructions
(3AXD50000048633 [English]). If you ignore the safety instructions, injury
or death, or damage to the equipment can occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
6
Start-up 59
12
Содержание ACS880-307LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 307LC diode supply units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...12 ...
Страница 34: ...34 ...
Страница 40: ...11 Reinstall the shrouding removed earlier 12 Close the door 3 PE PE 40 Electrical installation ...
Страница 41: ...10 9 7 6 8 Electrical installation 41 11 ...
Страница 73: ...11 12 12 6 10 Maintenance 73 ...
Страница 78: ...78 ...
Страница 88: ...88 ...
Страница 96: ... 400 mm wide input cubicle 96 Technical data ...
Страница 97: ... 600 mm wide incoming cubicle or input cubicle Technical data 97 ...