Description
Terminal
Temp fault
(0 = overtemperature)
DI1
1
5
6
7
1
2
3
4
Run enable
(1 = run enable)
DI2
2
MCB feedback
(0 = main contactor/breaker open)
DI3
3
Auxiliary circuit breaker fault
DI4
4
Not in use by default. Can be used for eg. earth fault monitoring.
DI5
5
(0 -> 1 = fault reset)
DI6
6
Not in use by default. Can be used for eg. emergency stop.
DIIL
7
Digital input/outputs
XDIO
Not in use by default
DIO1
1
1
2
3
4
Not in use by default
DIO2
2
Digital input/output ground
DIOGND
3
Digital input/output ground
DIOGND
4
Auxiliary voltage output
XD24
+24 V DC 200 mA
5)
+24VD
1
5
6
7
8
Digital input ground
DICOM
2
+24 V DC 200 mA
+24VD
3
Digital input/output ground
DIOGND
4
Ground selection switch
6)
DICOM=DIOGND
ON
OFF
Analog inputs, reference voltage output
XAI
10 V DC,
R
L
1…10 kohm
+VREF
1
5
6
7
1
2
3
4
-10 V DC,
R
L
1…10 kohm
-VREF
2
Ground
AGND
3
Not in use by default. 0(2)…10 V,
R
in
> 200 kohm
7)
AI1+
4
AI1-
5
Not in use by default. 0(4)…20 mA,
R
in
= 100 ohm
8)
AI2+
6
AI2-
7
AI1 current/voltage selection switch
AI1
I
U
AI2 current/voltage selection switch
AI2
I
U
Analog outputs
XAO
Zero
(no signal indicated)
0…20 mA,
R
L
< 500 ohm
AO1
1
1
2
3
4
AGND
2
Zero
(not signal indicated)
0…20 mA,
R
L
< 500 ohm
AO2
3
AGND
4
External power input
XPOW
24 V DC, 2.05 A
+24VI
1
1
2
3
4
GND
2
+24VI
3
GND
4
Not in use in supply units
X12
Control panel connection
X13
The control unit 51
Содержание ACS880-307LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 307LC diode supply units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...12 ...
Страница 34: ...34 ...
Страница 40: ...11 Reinstall the shrouding removed earlier 12 Close the door 3 PE PE 40 Electrical installation ...
Страница 41: ...10 9 7 6 8 Electrical installation 41 11 ...
Страница 73: ...11 12 12 6 10 Maintenance 73 ...
Страница 78: ...78 ...
Страница 88: ...88 ...
Страница 96: ... 400 mm wide input cubicle 96 Technical data ...
Страница 97: ... 600 mm wide incoming cubicle or input cubicle Technical data 97 ...