1.
Remove shrouding to access the cable entries and trunking inside the cubicle.
2.
Run the control cables into the cubicle. If possible, arrange for a 360° grounding
of the cable shield at the cable entry.
If the outer surface of the shield is non-conductive, turn the shield inside out as
shown below and wrap copper foil around the cable to keep the shielding
continuous. Do not cut the grounding wire (if present).
1
A
B
C
2
2
3
4
Stripped cable
A
Conductive surface of the shield exposed
B
Stripped part covered with copper foil
C
Cable shield
1
Copper foil
2
Shielded twisted pair
3
Grounding wire
4
Copper cable
5
3.
Run the cables to the control unit (or other connection point). Use the existing
trunking wherever possible.
4.
Cut the cables to suitable length.
5.
Strip the cable ends and conductors. When connecting to the drive I/O, also remove
the shield along with the outer sheathing, and use electrical tape or shrink tubing
to contain the strands. Elsewhere, twist the outer shield strands into a bundle,
crimp a lug onto it and connect it to the nearest chassis grounding point.
78 Electrical installation
6. Strip the cable ends and conductors. When connecting to the drive I/O, also remove
the shield along with the outer sheathing, and use electrical tape or shrink tubing to
contain the strands. Elsewhere, twist the outer shield strands into a bundle, crimp a
lug onto it and connect it to the nearest chassis grounding point.
7. Connect the conductors to appropriate terminals (see the circuit diagrams delivered
with the unit).
8. Fasten the shrouds (if any).
9. Close the doors.
2
3 4
1
1
2
3
4
5
Keep as short as possible
1
SHIELD*
2
If no dedicated “shield” connect-
or is provided, ground the inner
cable shields to the chassis.
3
At the other end of the cable,
leave the shield unconnected, or
connect it to ground via a capa-
citor with a value of a few nano-
farads.
4
Where grounding clamps are not
available, twist the shield
strands into a bundle, crimp a
lug terminal onto it and fasten
the lug to the chassis. Secure the
cable into place with eg. cable
ties.
5
Electrical installation 69
11
Содержание ACS880-304LC Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 304LC A019 diode supply modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 30: ...30 ...
Страница 34: ...34 ...
Страница 45: ... Kits for D8D supply modules in 400 mm Rittal VX25 or generic enclosure Cabinet construction 45 10 ...
Страница 46: ... Stage 1 Installation of common parts 46 Cabinet construction ...
Страница 47: ... Stage 2 Module installation parts Cabinet construction 47 10 ...
Страница 48: ... Stage 3 Liquid cooling system components 48 Cabinet construction ...
Страница 49: ... Stage 4 AC and DC busbar installation Cabinet construction 49 10 ...
Страница 50: ... Stage 5 AC and DC connection 50 Cabinet construction ...
Страница 51: ... Stage 6 Cabinet fan and heat exchanger Cabinet construction 51 10 ...
Страница 52: ... Stage 7 Shroud installation parts 52 Cabinet construction ...
Страница 53: ... Stage 8 Door covers and explosion exhaust kit Cabinet construction 53 10 ...
Страница 54: ...54 ...
Страница 74: ...74 ...
Страница 87: ...5 Maintenance 87 ...
Страница 88: ...6 7 8 9 9 88 Maintenance ...
Страница 92: ...92 ...
Страница 108: ...108 ...
Страница 118: ...118 ...
Страница 140: ...Liquid cooled D8D module Dimensions in mm 1 mm 0 0394 in 140 Dimension drawings ...
Страница 142: ...ZCU 14 control unit 142 Dimension drawings ...
Страница 143: ...Support plate for ZCU 14 UDZKROH 0 GRZQ UDZKROH 0 GRZQ Dimension drawings 143 ...
Страница 144: ...CIO 01 module 144 Dimension drawings ...
Страница 152: ...152 ...