Draining the internal cooling circuit
The modules in each cubicle can be drained through the drain valves without draining
the whole internal cooling circuit.
WARNING!
Hot, pressurized coolant can be present in the cooling circuit. Do not work on
the cooling circuit before the pressure is released by stopping the pumps and
draining coolant.
1.
Attach hoses to each drain valve in the cubicle to be drained. Lead the hoses into
a suitable container. Make sure the ends of the hoses are not immersed in coolant
at any point so that air can displace the coolant in the system.
2.
Open the drain valves. Wait until all coolant has drained.
Note: Draining coolant into the sewer system is not allowed.
3.
If required, dry the piping with compressed oil-free air of less than 6 bar.
4.
If the drive is to be stored in temperatures below 0 °C (32 °F),
•
dry the cooling circuit with air,
•
fill the cooling circuit with coolant specified under
.
•
drain the cooling circuit again.
Maintenance intervals
As a general rule, the quality of the coolant should be checked at intervals of two years.
This can be done by distributors of Antifrogen® L (see
) if a 250
milliliter sample is provided.
Technical data
■
Coolant specification
Coolant type
Antifrogen® L (by Clariant International Ltd,
) 25% or 50% mixture,
available from Clariant distributors and ABB Service representatives.
Note: Do not dilute the coolant. It is ready to use.
Antifrogen® L 25% mixture is usable in storage temperatures down to -16 °C (3.2 °F).
Antifrogen® L 50% mixture is usable in storage temperatures down to -40 °C (-40 °F).
Note that operation below 0 °C (32 °F) is not permitted regardless of the freezing
point of the coolant.
WARNING!
The warranty does not cover damage that occurs from the use of incorrect
coolant.
■
Temperature limits
Freeze protection: The freezing point of the coolant is determined by the concentration
of heat transfer fluid in the mixture.
114 Internal cooling circuit
Содержание ACS880-304LC Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 304LC A019 diode supply modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 30: ...30 ...
Страница 34: ...34 ...
Страница 45: ... Kits for D8D supply modules in 400 mm Rittal VX25 or generic enclosure Cabinet construction 45 10 ...
Страница 46: ... Stage 1 Installation of common parts 46 Cabinet construction ...
Страница 47: ... Stage 2 Module installation parts Cabinet construction 47 10 ...
Страница 48: ... Stage 3 Liquid cooling system components 48 Cabinet construction ...
Страница 49: ... Stage 4 AC and DC busbar installation Cabinet construction 49 10 ...
Страница 50: ... Stage 5 AC and DC connection 50 Cabinet construction ...
Страница 51: ... Stage 6 Cabinet fan and heat exchanger Cabinet construction 51 10 ...
Страница 52: ... Stage 7 Shroud installation parts 52 Cabinet construction ...
Страница 53: ... Stage 8 Door covers and explosion exhaust kit Cabinet construction 53 10 ...
Страница 54: ...54 ...
Страница 74: ...74 ...
Страница 87: ...5 Maintenance 87 ...
Страница 88: ...6 7 8 9 9 88 Maintenance ...
Страница 92: ...92 ...
Страница 108: ...108 ...
Страница 118: ...118 ...
Страница 140: ...Liquid cooled D8D module Dimensions in mm 1 mm 0 0394 in 140 Dimension drawings ...
Страница 142: ...ZCU 14 control unit 142 Dimension drawings ...
Страница 143: ...Support plate for ZCU 14 UDZKROH 0 GRZQ UDZKROH 0 GRZQ Dimension drawings 143 ...
Страница 144: ...CIO 01 module 144 Dimension drawings ...
Страница 152: ...152 ...