Operation principle and hardware
description
Contents of this chapter
This chapter describes how the diode supply unit works and the hardware of the diode
supply module.
Operation principle
The heart of the diode supply unit is a diode bridge. It rectifies three-phase AC current
to direct current for the intermediate DC link of the drive. The intermediate DC link
supplies the inverters that run the motors. There can be one inverter unit only (single
drives) or several inverter units (multidrives) connected to the intermediate circuit.
The rectifier bridge in the supply module is uncontrolled: it cannot control the DC link
voltage or limit the charging current of the DC link capacitors at the power up. Thus
you can only use the bridge with inverters that have charging circuits, or you must
equip the supply unit with a separate charging circuit.
Note:
•
The supply module does not have means to control, limit or cut off the load current.
•
The customer must arrange the overload and short-circuit protection of each
supply cable (typically with fuses).
•
The supply unit does not have AC or DC chokes. Thus, the customer must arrange
a sufficient inductance at the AC side of each supply module with suitable cabling.
The minimum length of the supply cable per each supply module is 5 meters (16.4
feet). The inductances between the parallel-connected supply modules must be
identical, ie, the cabling to each module must be identical in regard to cable type
and length. For selecting the supply transformer, see
.
2
Operation principle and hardware description 15
Содержание ACS880-304LC Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 304LC A019 diode supply modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 30: ...30 ...
Страница 34: ...34 ...
Страница 45: ... Kits for D8D supply modules in 400 mm Rittal VX25 or generic enclosure Cabinet construction 45 10 ...
Страница 46: ... Stage 1 Installation of common parts 46 Cabinet construction ...
Страница 47: ... Stage 2 Module installation parts Cabinet construction 47 10 ...
Страница 48: ... Stage 3 Liquid cooling system components 48 Cabinet construction ...
Страница 49: ... Stage 4 AC and DC busbar installation Cabinet construction 49 10 ...
Страница 50: ... Stage 5 AC and DC connection 50 Cabinet construction ...
Страница 51: ... Stage 6 Cabinet fan and heat exchanger Cabinet construction 51 10 ...
Страница 52: ... Stage 7 Shroud installation parts 52 Cabinet construction ...
Страница 53: ... Stage 8 Door covers and explosion exhaust kit Cabinet construction 53 10 ...
Страница 54: ...54 ...
Страница 74: ...74 ...
Страница 87: ...5 Maintenance 87 ...
Страница 88: ...6 7 8 9 9 88 Maintenance ...
Страница 92: ...92 ...
Страница 108: ...108 ...
Страница 118: ...118 ...
Страница 140: ...Liquid cooled D8D module Dimensions in mm 1 mm 0 0394 in 140 Dimension drawings ...
Страница 142: ...ZCU 14 control unit 142 Dimension drawings ...
Страница 143: ...Support plate for ZCU 14 UDZKROH 0 GRZQ UDZKROH 0 GRZQ Dimension drawings 143 ...
Страница 144: ...CIO 01 module 144 Dimension drawings ...
Страница 152: ...152 ...