Guidelines for planning the electrical installation 61
Additional requirements for non-ABB high-output and IP23 motors
The rated output power of high output motors is higher than what is stated for the particular
frame size in EN 50347:2001. The table below shows the requirements for random-wound
and form-wound non-ABB motors with nominal power smaller than 350 kW. For bigger
motors, consult the motor manufacturer.
Nominal AC
supply voltage
Requirement for
Motor insulation system
ABB d
u
/d
t
filter, insulated N-end bearing and
ABB common mode filter
100 kW <
P
N
<
350 kW or
IEC 315 < frame size < IEC 400
134 hp <
P
N
<
469 hp or
NEMA 500 < frame size <
NEMA 580
U
N
< 420 V
Standard:
Û
LL
= 1300 V
+ N + CMF
1)
420 V <
U
N
< 500 V Standard:
Û
LL
= 1300 V
+ N + d
u
/d
t
+ CMF
or
Reinforced:
Û
LL
= 1600 V,
0.2 microsecond rise time
+ N + CMF
1)
500 V <
U
N
< 600 V Reinforced:
Û
LL
= 1600 V
+ d
u
/d
t
+ N + CMF
or
Reinforced:
Û
LL
= 1800 V
+ N + CMF
1)
600 V <
U
N
< 690 V Reinforced:
Û
LL
= 1800 V
+ N + d
u
/d
t
+ CMF
Reinforced:
Û
LL
= 2000 V,
0.3 microsecond rise time
***
N + CMF
1)
*** If the intermediate DC circuit voltage of the drive is increased from the nominal level by resistor
braking, check with the motor manufacturer if additional output filters are needed in the applied
drive operation range.
1)
also d
u
/d
t
filter is required at the output of the basic drive modules if the motor cable length is
less than 20 meters before connecting the motor cables together
Содержание ACS880-07XT Series
Страница 1: ...ABB industrial drives Hardware manual ACS880 07XT drives 400 to 1200 kW ...
Страница 4: ......
Страница 12: ...12 ...
Страница 20: ...20 Safety instructions ...
Страница 26: ...26 Introduction to the manual ...
Страница 47: ...Mechanical installation 47 Moving the crate with a forklift Free width for fork tines 750 mm 29 5 ...
Страница 54: ...54 Mechanical installation ...
Страница 89: ...Electrical installation 89 PE 11 8 4 9 11 ...
Страница 94: ...94 Electrical installation ...
Страница 110: ...110 Start up Test and validate the operation of Prevention of unexpected start with FSO xx option Q950 Action ...
Страница 112: ...112 Fault tracing ...
Страница 123: ...Maintenance 123 5 6 7 ...
Страница 124: ...124 Maintenance 8 10 9 ...
Страница 126: ...126 Maintenance 6 5 4 ...
Страница 127: ...Maintenance 127 9 8 7 ...
Страница 128: ...128 Maintenance 12 11 10 ...
Страница 149: ...Dimensions 149 Dimension drawing examples Frame 2 R11 R10 with brake chopper ...
Страница 150: ...150 Dimensions Frame 2 R11 R10 without brake chopper ...
Страница 153: ...Dimensions 153 Location of input terminals ACS880 07XT 12 pulse ...
Страница 154: ...154 Dimensions Location of output terminals ACS880 07XT R10 with du dt ...
Страница 155: ...Dimensions 155 Location of output terminals ACS880 07XT R10 without du dt ...
Страница 156: ...156 Dimensions Location of output terminals ACS880 07XT R11 with du dt ...
Страница 157: ...Dimensions 157 Location of output terminals ACS880 07XT R11 without du dt ...
Страница 158: ...158 Dimensions Location of PE terminals ACS880 07XT ...
Страница 159: ...Dimensions 159 Location of resistor terminals ACS880 07XT R10 ...
Страница 160: ...160 Dimensions Location of resistor terminals ACS880 07XT R11 ...
Страница 168: ...www abb com drives www abb com drivespartners 3ABD00043579 Rev C EN 2018 01 01 Contact us ...