140 Technical data
Efficiency
96.0 … 98.0% at nominal power level depending on drive type
Protection classes
Degrees of protection
(IEC/EN 60529)
IP22 (standard), IP42 (optional),IP54(pending)
Overvoltage category
(IEC 60664-1)
III
Protective class
(IEC/EN 61800-5-1)
I
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated, indoor, controlled
environment.
Operation
installed for stationary
use
Storage
in the protective package
Transportation
in the protective package
Installation site altitude
0 to 2000 m above sea
level.
For attitude over 2000m,
contact ABB.
Output derated above
1000 m (3281 ft). See
section
drive modules with 50 Hz
and 60 Hz supply are
given below.
.
-
-
Air temperature
0 … +40 °C
(+32 … +104 °F). No
condensation allowed.
Output derated in the
range +40 … +50 °C
(+104 … +122 °F). See
.
-40 to +70 °C
(-40 to +158 °F)
-40 to +70 °C
(-40 to +158 °F)
Relative humidity
Max. 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
Contamination
IEC/EN 60721-3-3:2002:
Classification of
environmental conditions
- Part 3-3: Classification
of groups of
environmental
parameters and their
severities - Stationary
use of weather protected
locations
IEC 60721-3-1:1997
IEC 60721-3-2:1997
Chemical gases
Class 3C2
Class 1C2
Class 2C2
Solid particles
Class 3S2. No
conductive dust allowed.
Class 1S3 (packing must
support this, otherwise
1S2)
Class 2S2
Содержание ACS880-07XT Series
Страница 1: ...ABB industrial drives Hardware manual ACS880 07XT drives 400 to 1200 kW ...
Страница 4: ......
Страница 12: ...12 ...
Страница 20: ...20 Safety instructions ...
Страница 26: ...26 Introduction to the manual ...
Страница 47: ...Mechanical installation 47 Moving the crate with a forklift Free width for fork tines 750 mm 29 5 ...
Страница 54: ...54 Mechanical installation ...
Страница 89: ...Electrical installation 89 PE 11 8 4 9 11 ...
Страница 94: ...94 Electrical installation ...
Страница 110: ...110 Start up Test and validate the operation of Prevention of unexpected start with FSO xx option Q950 Action ...
Страница 112: ...112 Fault tracing ...
Страница 123: ...Maintenance 123 5 6 7 ...
Страница 124: ...124 Maintenance 8 10 9 ...
Страница 126: ...126 Maintenance 6 5 4 ...
Страница 127: ...Maintenance 127 9 8 7 ...
Страница 128: ...128 Maintenance 12 11 10 ...
Страница 149: ...Dimensions 149 Dimension drawing examples Frame 2 R11 R10 with brake chopper ...
Страница 150: ...150 Dimensions Frame 2 R11 R10 without brake chopper ...
Страница 153: ...Dimensions 153 Location of input terminals ACS880 07XT 12 pulse ...
Страница 154: ...154 Dimensions Location of output terminals ACS880 07XT R10 with du dt ...
Страница 155: ...Dimensions 155 Location of output terminals ACS880 07XT R10 without du dt ...
Страница 156: ...156 Dimensions Location of output terminals ACS880 07XT R11 with du dt ...
Страница 157: ...Dimensions 157 Location of output terminals ACS880 07XT R11 without du dt ...
Страница 158: ...158 Dimensions Location of PE terminals ACS880 07XT ...
Страница 159: ...Dimensions 159 Location of resistor terminals ACS880 07XT R10 ...
Страница 160: ...160 Dimensions Location of resistor terminals ACS880 07XT R11 ...
Страница 168: ...www abb com drives www abb com drivespartners 3ABD00043579 Rev C EN 2018 01 01 Contact us ...