40 Technical data
Rectifier power capacity (
P
rec,ave
and
P
rec,max
)
U
ac
: AC input voltage.
P
rec,ave
is the average rectifier power capacity of the drive over a 3-minutes time window. The average power
taken from AC power line must be lower than this value during any 3-minutes time window.
1)
Value 630 applies to 600…690 V AC.
P
rec,max
is the maximum rectifier power capacity of the drive allowed for max. 10 s. The instantaneous power
taken from AC power line must never exceed this limit.
R5a: ACS880-01 types -07A3-7, -09A8-7, -14A2-7 and -018A-7.
R5b: ACS880-01 types -022A-7, -026A-7, -035A-7, -042A-7 and -049A-7.
R10a: ACS880-04 types -505A-3 and -460A-5.
R10b: ACS880-04 types -585A-3, -650A-3, -583A-5, -635A-5, -330A-7
and -370A-7.
Frame
P
rec,ave
P
rec,max
depending on
U
ac
208…240 V AC
(ACS880-01
-xxxx-2)
380…415 V AC
(ACS880-01/-04
-xxxx-3)
380…500 V AC
(ACS880-01/-04
-xxxx-5)
600…690 V AC
(ACS880-01/-04
-xxxx-7)
R1
5.5
7
7
6
-
R2
11
13
13
10
-
R3
18.5
26
26
24
-
R4
30
37
37
32
-
R5a
15
-
-
-
24
R5b
45
63
63
59
54
R6
75
92
92
79
81
R7
110
153
153
144
150
R8
160
228
228
212
208
R9
250
-
317
262
304
R10a
250
-
340
420
-
R10b
355
-
420
500
510
R11
500/630
1)
-
620
700
850
Содержание ACS880-04 drive modules
Страница 1: ...ABB industrial drives Application guide ACS880 01 drives and ACS880 04 drive modules Common DC systems...
Страница 4: ......
Страница 10: ...10 Introduction to the manual...
Страница 16: ...16 Operation principle and hardware description...
Страница 30: ...30 Planning basics...
Страница 38: ...38 Planning additional instructions...
Страница 48: ...Contact us www abb com drives www abb com drivespartners 3AUA0000127818 Rev B EN 2014 04 17...