42 Technical data
Frames R10 to R11
R10a: ACS880 types -505A-3 and -460A-5.
R10b: ACS880 types -585A-3, -650A-3, -583A-5, -635A-5,
-330A-7
and -370A-7.
U
ac
: AC input voltage.
DC contactors between the drives
Tables below show when you need a DC contactor between the drives in the DC link. If
both frame sizes exist in the common DC system, and both of them are connected to the
AC power line, you must have a DC contactor between the DC terminals of these drives.
The DC contactor must isolate the drives until charging is complete.
Frames R1 to R5
Frames R5 to R9
Frames R10 to R11
R10a: ACS880 types -505A-3 and -460A-5.
R10b: ACS880 types -585A-3, -650A-3, -583A-5, -635A-5, -330A-7 and -370A-7.
Frame
R10a
R10b
R11
R10a
0.9
0.7
0.5
R10b
0.7
0.9
0.9
R11
0.5
0.9
0.9
Contactor is not needed.
X
Contactor is needed.
The smaller drive may not be connected to the AC power line.
Frame
R1
R2
R3
R4
R5
R1
R2
X
R3
X
R4
X
R5
X
X
X
Frame
R5
R6
R7
R8
R9
R5
R6
R7
R8
R9
Frame
R10a
R10b
R11
R10a
R10b
R11
Содержание ACS880-04 drive modules
Страница 1: ...ABB industrial drives Application guide ACS880 01 drives and ACS880 04 drive modules Common DC systems...
Страница 4: ......
Страница 10: ...10 Introduction to the manual...
Страница 16: ...16 Operation principle and hardware description...
Страница 30: ...30 Planning basics...
Страница 38: ...38 Planning additional instructions...
Страница 48: ...Contact us www abb com drives www abb com drivespartners 3AUA0000127818 Rev B EN 2014 04 17...