Technical data 43
Charging resistance values
R
: Charging resistance of the drive module.
R
min
: Minimum resistance that the charging circuit can supply (in case the circuit must supply charging current
of several drives).
Charging circuit
E
r
values
E
r
: Maximum energy pulse that the charging circuit of the drive can withstand.
DC link capacitance values
U
ac
: AC input voltage.
R5a: ACS880-01 types -07A3-7, -09A8-7, -14A2-7 and -018A-7.
R5b: ACS880-01 types -022A-7, -026A-7, -035A-7, -042A-7 and -049A-7.
Frame
R
[ohm]
R
min
[ohm]
R1, R2, R3
50
16
R4
25 6
R5
20
N/A
R6, R7
36
N/A
R8, R9
18
N/A
R10
3.3
N/A
R11
10
N/A
Frame
E
r
[J]
R5
411
R6
1400
R7
1400
R8
5600
R9
5600
R10
5600
R11
7400
Frame
C
DC
[microF] depending on
U
ac
208…240 V AC
(ACS880-01
-xxxx-2)
380…415 V AC
(ACS880-01/-04
-xxxx-3)
380…500 V AC
(ACS880-01/-04
-xxxx-5)
600…690 V AC
(ACS880-01/-04
-xxxx-7)
R1
300
300
300
-
R2
500
500
500
-
R3
1000
1000
1000
-
R4
4100
1000
1000
-
R5a
-
-
-
350
R5b
6200
1500
1500
700
R6
10500
2600
2600
1200
R7
15300
3800
3800
1700
R8
22500
5600
5600
2500
R9
-
8800
8800
3900
R10
-
15800
15800
5267
R11
-
23700
23700
10533
Содержание ACS880-04 drive modules
Страница 1: ...ABB industrial drives Application guide ACS880 01 drives and ACS880 04 drive modules Common DC systems...
Страница 4: ......
Страница 10: ...10 Introduction to the manual...
Страница 16: ...16 Operation principle and hardware description...
Страница 30: ...30 Planning basics...
Страница 38: ...38 Planning additional instructions...
Страница 48: ...Contact us www abb com drives www abb com drivespartners 3AUA0000127818 Rev B EN 2014 04 17...