Fault tracing 239
0050
ENCODER 1 CABLE
(0x7389)
Programmable fault:
Encoder 1 cable fault detected. Check cable between FEN-xx interface
and encoder 1. After any modifications in
cabling, re-configure interface by
switching drive power off and on, or by
activating parameter
0051
ENCODER 2 CABLE
(0x738A)
Programmable fault:
Encoder 2 cable fault detected. Check cable between FEN-xx interface
and encoder 2. After any modifications in
cabling, re-configure interface by
switching drive power off and on, or by
activating parameter
0052
D2D CONFIG
(0x7583)
Configuration of the drive-to-
drive link has failed for a
reason other than those
indicated by alarm A-
, for
example start inhibition is
requested but not granted.
Contact your local ABB representative.
0053
D2D COMM
(0x7520)
Programmable fault:
On the master drive: The drive
has not been replied to by an
activated follower for five
consecutive polling cycles.
Check that all drives that are polled
(parameters
) on the drive-to-
drive link are powered, properly
connected to the link, and have the
correct node address.
Check the drive-to-drive link wiring.
On a follower drive: The drive
has not received new
reference 1 and/or 2 for five
consecutive reference
handling cycles.
Check the settings of parameters
) on the
master drive.
Check the drive-to-drive link wiring.
0054
D2D BUF OVLOAD
(0x7520)
Programmable fault:
Transmission of drive-to-drive
references failed because of
message buffer overflow.
Contact your local ABB representative.
0055
TECH LIB
(0x6382)
Resettable fault generated by
a technology library.
Refer to the documentation of the
technology library.
0056
TECH LIB CRITICAL
(0x6382)
Permanent fault generated by
a technology library.
Refer to the documentation of the
technology library.
0057
FORCED TRIP
(0xFF90)
Generic Drive Communication
Profile trip command.
Check PLC status.
0058
FB PAR ERROR
(0x6320)
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter group
.
0059
STALL
(0x7121)
Programmable fault:
Motor is operating in stall
region because of e.g.
excessive load or insufficient
motor power.
Check motor load and drive ratings.
Check fault function parameters.
0060
LOAD CURVE
(0x2312)
Programmable fault:
/
Overload or underload limit
has been exceeded.
Check the settings of the parameters in
group
Code
Fault
(fieldbus code)
Cause
What to do
Содержание ACS850 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 2: ......
Страница 4: ......
Страница 24: ...24 Start up...
Страница 28: ...28 Control locations and operating modes...
Страница 252: ...252 Fieldbus control...