168 Parameters
38.06
U/f curve freq3
Defines the frequency at the 3rd point on the custom
U/f
curve in percent of parameter
1 … 500%
3rd point, frequency.
1 = 1%
38.07
U/f curve freq4
Defines the frequency at the 4th point on the custom
U/f
curve in percent of parameter
1 … 500%
4th point, frequency.
1 = 1%
38.08
U/f curve freq5
Defines the frequency at the 5th point on the custom
U/f
curve in percent of parameter
1 … 500%
5th point, frequency.
1 = 1%
38.09
U/f curve volt1
Defines the voltage at the 1st point on the custom
U/f
curve in
percent of parameter
.
0 … 200%
1st point, voltage.
1 = 1%
38.10
U/f curve volt2
Defines the voltage at the 2nd point on the custom
U/f
curve
in percent of parameter
0 … 200%
2nd point, voltage.
1 = 1%
38.11
U/f curve volt3
Defines the voltage at the 3rd point on the custom
U/f
curve in
percent of parameter
.
0 … 200%
3rd point, voltage.
1 = 1%
38.12
U/f curve volt4
Defines the voltage at the 4th point on the custom
U/f
curve in
percent of parameter
.
0 … 200%
4th point, voltage.
1 = 1%
38.13
U/f curve volt5
Defines the voltage at the 5th point on the custom
U/f
curve in
percent of parameter
.
0 … 200%
5th point, voltage.
1 = 1%
40
40 Motor control
Motor control settings.
40.01
Motor noise
An optimization setting for balancing between control
performance and motor noise level.
Cyclic
Maximizes inverter overloadability.
0
Low noise
Minimizes motor noise.
1
Long cable
Control performance optimized for long motor cables.
2
40.03
Slip gain
Defines the slip gain which is used to improve the estimated
motor slip. 100% means full slip gain; 0% means no slip gain.
The default value is 100%. Other values can be used if a
static speed error is detected despite of the full slip gain.
Example
(with nominal load and nominal slip of 40 rpm): A
1000 rpm constant speed reference is given to the drive.
Despite of the full slip gain (= 100%), a manual tachometer
measurement from the motor axis gives a speed value of 998
rpm. The static speed error is 1000 rpm - 998 rpm = 2 rpm. To
compensate the error, the slip gain should be increased. At
the 105% gain value, no static speed error exists (2 rpm / 40
rpm = 5%).
0 … 200%
Slip gain.
1 = 1%
No.
Name/Value
Description
FbEq