96 Parameters
Spd ref Safe
The drive generates an AI SUPERVISION alarm and sets the
speed to the speed defined by parameter
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
Last speed
The drive generates an AI SUPERVISION alarm and freezes
the speed to the level the drive was operating at. The speed
is determined by the average speed over the previous 10
seconds.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
13.33
AI superv cw
Selects the analogue input signal supervision limit.
Example:
If parameter value is set to 0b0010, bit 1 AI1>max
is selected.
14
14 Digital I/O
Configuration of digital input/outputs and relay outputs.
14.01
DI invert mask
Inverts status of digital inputs as reported by
14.02
DIO1 conf
Selects whether DIO1 is used as a digital output or input.
Output
DIO1 is used as a digital output.
0
Input
DIO1 is used as a digital input.
1
14.03
DIO1 out src
Selects a drive signal to be connected to digital output DIO1
(when
is set to
).
Brake cmd
).
1073742608
Ready
1073743361
Enabled
1073808897
Started
1073874433
Running
1073939969
No.
Name/Value
Description
FbEq
Bit
Supervision
Action selected by parameter
is taken if
0
AI1<min
AI1 signal value falls below the value defined by equation: par.
- 0.5 mA or V
1
AI1>max
AI1 signal value exceeds the value defined by equation: par.
+ 0.5 mA or V
2
AI2<min
AI2 signal value falls below the value defined by equation: par.
- 0.5 mA or V
3
AI2>min
AI1 signal value exceeds the value defined by equation: par.
+ 0.5 mA or V
Bit
Name
0
1 = Invert DI1
1
1 = Invert DI2
2
1 = Invert DI3
3
1 = Invert DI4
4
1 = Invert DI5
5
1 = Invert DI6