230 Fault tracing
2032
ENCODER 2 CABLE
(0x738A)
Encoder 2 cable fault detected. Check cable between FEN-xx interface
and encoder 2. After any modifications in
cabling, re-configure interface by
switching drive power off and on, or by
activating parameter
2033
D2D
COMMUNICATION
(0x7520)
Programmable fault:
On the master drive: The drive
has not been replied to by an
activated follower for five
consecutive polling cycles.
Check that all drives that are polled
(parameters
and
) on the drive-to-
drive link are powered, properly
connected to the link, and have the
correct node address.
Check the drive-to-drive link wiring.
On a follower drive: The drive
has not received new
reference 1 and/or 2 for five
consecutive reference
handling cycles.
Check the settings of parameters
) on the
master drive.
Check the drive-to-drive link wiring.
2034
D2D BUFFER
OVERLOAD
(0x7520)
Programmable fault:
Transmission of drive-to-drive
references failed because of
message buffer overflow.
Contact your local ABB representative.
2035
PS COMM
(0x5480)
Communication errors
detected between the JCU
Control Unit and the power unit
of the drive.
Check the connections between the JCU
Control Unit and the power unit.
2036
RESTORE
(0x6300)
Restoration of backed-up
parameters failed.
Contact your local ABB representative.
2037
CUR MEAS
CALIBRATION
(0x2280)
Current measurement
calibration will occur at next
start.
Informative alarm.
2038
AUTOPHASING
(0x3187)
Autophasing will occur at next
start.
Informative alarm.
2039
EARTH FAULT
(0x2330)
Programmable fault:
Drive has detected load
unbalance typically due to
earth fault in motor or motor
cable.
Check there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check for an earth fault in motor or motor
cables by measuring the insulation
resistances of motor and motor cable.
If no earth fault can be detected, contact
your local ABB representative.
2040
AUTORESET
(0x6080)
A fault is to be autoreset.
Informative alarm. See parameter group
2041
MOTOR NOM VALUE
(0x6383)
The motor configuration
parameters are set incorrectly.
Check the settings of the motor
configuration parameters in group 99.
The drive is not dimensioned
correctly.
Check that the drive is sized correctly for
the motor.
2042
D2D CONFIG
(0x7583)
The settings of drive-to-drive
link configuration parameters
(group 57) are incompatible.
Check the settings of the parameters in
group
.
Code
Alarm
(fieldbus code)
Cause
What to do