154 Parameters
Pointer
Value pointer setting (see
on page
).
-
33.11
Superv3 hi
Selects the upper limit for supervision 3. See parameter
.
-32768.00 …
32768.00
Upper limit for supervision 3.
100 = 1
33.12
Superv3 lo
Selects the lower limit for supervision 3. See parameter
.
-32768.00 …
32768.00
Lower limit for supervision 3.
100 = 1
34
34 User load curve
Definition of user load curve. See also section
34.01
Overload func
Configures the supervision of the upper boundary of the user
load curve.
No.
Name/Value
Description
FbEq
Bit
Function
0
Ena sup (Enable supervision)
0 = Disabled: Supervision disabled.
1 = Enabled: Supervision enabled.
1
Input value sel (Input value selection)
0 = Current: Current is supervised.
1 = Torque: Torque is supervised.
2
Ena warn (Enable warning)
0 = Disabled
1 = Enabled: Drive generates an alarm when the curve is exceeded.
3
Ena fault (Enable fault)
0 = Disabled
1 = Enabled: Drive trips on a fault when the curve is exceeded.
4
Ena lim integ (Enable limit integration)
0 = Disabled
1 = Enabled: Integration time defined by parameter
is used. After
the supervision is evoked, the current or torque is limited by the upper boundary of the
load curve.
5
Ena lim always (Enable limit always)
0 = Disabled
1 = Enabled: The current or torque is always limited by the upper boundary of the load
curve.
Содержание ACS850 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 2: ......
Страница 4: ......
Страница 24: ...24 Start up...
Страница 28: ...28 Control locations and operating modes...
Страница 252: ...252 Fieldbus control...