Parameters 273
Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Done
Reset completed or not requested (normal operation).
0
All
Reset both the peak value logger and amplitude logger 2.
1
PVL
Reset the peak value logger.
2
AL2
Reset amplitude logger 2.
3
Peak value recorded by the peak value logger.
0.00
-32768.00…
32767.00
Peak value.
1 = 1
The date on which the peak value was recorded.
01.01.1980
-
Peak occurrence date.
-
The time at which the peak value was recorded.
00:00:01
-
Peak occurrence time.
-
Motor current at the moment the peak value was recorded.
0.00 A
-32768.00…
32767.00 A
Motor current at peak.
1 = 1 A
Voltage in the intermediate DC circuit of the drive at the
moment the peak value was recorded.
0.00 V
0.00…2000.00 V
DC voltage at peak.
10 = 1 V
Motor speed at the moment the peak value was recorded.
0.00 rpm
-30000.00…
30000.00 rpm
Motor speed at peak.
See par.
The date on which the peak value logger was last reset.
01.01.1980
-
Last reset date of the peak value logger.
-
The time at which the peak value logger was last reset.
00:00:01
-
Last reset time of the peak value logger.
-
Percentage of samples recorded by amplitude logger 1 that
fall between 0 and 10%. 100% corresponds to the
I
max
value
given in the ratings table in chapter Technical data in the
Hardware manual
.
0.00%
0.00…100.00%
Amplitude logger 1 samples between 0 and 10%.
1 = 1%
Percentage of samples recorded by amplitude logger 1 that
fall between 10 and 20%.
0.00%
0.00…100.00%
Amplitude logger 1 samples between 10 and 20%.
1 = 1%
Percentage of samples recorded by amplitude logger 1 that
fall between 20 and 30%.
0.00%
0.00…100.00%
Amplitude logger 1 samples between 20 and 30%.
1 = 1%
Percentage of samples recorded by amplitude logger 1 that
fall between 30 and 40%.
0.00%
0.00…100.00%
Amplitude logger 1 samples between 30 and 40%.
1 = 1%
Percentage of samples recorded by amplitude logger 1 that
fall between 40 and 50%.
0.00%
0.00…100.00%
Amplitude logger 1 samples between 40 and 50%.
1 = 1%
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 273 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...