If you equip the drive with a main contactor or breaker, make sure that it restores the
drive input power after a short break. The contactor must either re-connect after the
break automatically, or remain closed over the break. Depending on the contactor
control circuit design, this can require an additional hold circuit, uninterruptible auxiliary
power supply or auxiliary power supply buffering.
Note: If the power loss lasts so long that the drive trips on undervoltage, a fault reset
and a fresh start command is required to continue operation.
Implement the power-loss ride-through function as follows:
1.
Enable the power-loss ride-through function of the drive (parameter 30.31).
2.
If the installation is equipped with a main contactor, prevent its tripping at the
input power break. For example, use a time delay relay (hold) in the contactor
control circuit.
3.
Enable the automatic restart of the motor after a short power supply break:
•
Set the start mode to automatic (parameter 21.01 or 21.19, depending on the
motor control mode being used).
•
Define the automatic restart time (parameter 21.18).
WARNING!
Make sure that a flying restart of the motor will not cause any danger. If you
are in doubt, do not implement the power loss ride-through function.
Using power factor compensation capacitors with the
drive
Power factor compensation is not needed with AC drives. However, if a drive is to be
connected in a system with compensation capacitors installed, note the following
restrictions.
WARNING!
Do not connect power factor compensation capacitors or harmonic filters to
the motor cables (between the drive and the motor). They are not meant to be
used with AC drives and can cause permanent damage to the drive or
themselves.
If there are power factor compensation capacitors in parallel with the input of the
drive:
1.
Do not connect a high-power capacitor to the power line while the drive is
connected. The connection will cause voltage transients that may trip or even
damage the drive.
2.
If capacitor load is increased/decreased step by step when the AC drive is
connected to the power line, make sure that the connection steps are low enough
not to cause voltage transients that would trip the drive.
3.
Make sure that the power factor compensation unit is suitable for use in systems
with AC drives, ie, harmonic generating loads. In such systems, the compensation
unit should typically be equipped with a blocking reactor or harmonic filter.
94 Guidelines for planning the electrical installation
Содержание ACS580-04
Страница 1: ... ABB GENERAL PURPOSE DRIVES ACS580 04 drive modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 26: ...26 ...
Страница 60: ...60 ...
Страница 69: ...2 1 Tapping screw M6 12 Torx T30 Hex 9 N m 6 6 lbf ft Mechanical installation 69 10 ...
Страница 72: ...72 ...
Страница 100: ...100 ...
Страница 120: ...120 ...
Страница 128: ...2 7a 7b 5 3 3 7a 7b 8a 8b 8b 4 128 Installation example with full cabling panels option H381 ...
Страница 133: ...Installation example with full cabling panels option H381 133 ...
Страница 134: ...134 ...
Страница 146: ...146 ...
Страница 157: ...External control unit option P906 157 ...
Страница 158: ...Dimension drawing The dimensions are in millimeters and inches 158 External control unit option P906 ...
Страница 162: ...162 ...
Страница 164: ...164 ...
Страница 200: ...R10 standard configuration 200 Dimension drawings ...
Страница 201: ...R10 with options E208 0H354 H356 H370 0H371 Dimension drawings 201 ...
Страница 202: ...R10 with option B051 202 Dimension drawings ...
Страница 203: ...R10 with options E208 H356 P906 Dimension drawings 203 ...
Страница 204: ...R10 with options E208 0H371 H356 0H354 H370 P906 204 Dimension drawings ...
Страница 205: ...R10 with options B051 P906 Dimension drawings 205 ...
Страница 207: ...R10 Cabling panels H381 installed into a Rittal VX25 enclosure 3AXD50000439317 Dimension drawings 207 ...
Страница 208: ...R11 standard configuration 208 Dimension drawings ...
Страница 209: ...R11 with options E208 0H371 H356 0H354 H370 Dimension drawings 209 ...
Страница 210: ...R11 with option B051 210 Dimension drawings ...
Страница 211: ...R11 with options E208 H356 P906 Dimension drawings 211 ...
Страница 212: ...R11 with options E208 0H371 H356 0H354 H370 P906 212 Dimension drawings ...
Страница 213: ...R11 with options B051 P906 Dimension drawings 213 ...
Страница 215: ...R11 Cabling panels H381 installed into a Rittal VX25 enclosure 3AXD50000438938 Dimension drawings 215 ...
Страница 248: ...248 ...
Страница 254: ...Dimension drawings The dimensions are in millimeters 254 CAIO 01 bipolar analog I O adapter module ...
Страница 260: ...260 ...
Страница 265: ...CHDI 01 115 230 V digital input extension module 265 ...
Страница 266: ...266 ...
Страница 272: ...272 CMOD 01 multifunction extension module external 24 V AC DC and digital I O ...
Страница 278: ...278 ...
Страница 280: ...280 ...