Start-up including validation test
To ensure the safe operation of a safety function, validation is required. The final
assembler of the machine must validate the function by performing a validation test.
The test must be performed
1.
at initial start-up of the safety function
2.
after any changes related to the safety function (circuit boards, wiring,
components, settings, replacement of inverter module, etc.)
3.
after any maintenance work related to the safety function
4.
after a drive firmware update
5.
at the proof test of the safety function.
■
Competence
The validation test of the safety function must be carried out by a competent person
with adequate expertise and knowledge of the safety function as well as functional
safety, as required by IEC 61508-1 clause 6. The test procedures and report must be
documented and signed by this person.
■
Validation test reports
Signed validation test reports must be stored in the logbook of the machine. The
report shall include documentation of start-up activities and test results, references
to failure reports and resolution of failures. Any new validation tests performed due
to changes or maintenance shall be logged into the logbook.
■
Validation test procedure
After wiring the Safe torque off function, validate its operation as follows.
Note: If a CPTC-02 or an FSPS-21 module is installed, refer to its documentation.
Action
WARNING!
Obey the safety instructions. If you ignore them, injury or death, or damage to the equip-
ment can occur.
Make sure that the motor can be run and stopped freely during start-up.
Stop the drive (if running), switch the input power off and isolate the drive from the power line
using a disconnector.
Check the STO circuit connections against the wiring diagram.
Close the disconnector and switch the power on.
Test the operation of the STO function when the motor is stopped.
• Give a stop command for the drive (if running) and wait until the motor shaft is at a standstill.
Make sure that the drive operates as follows:
• Open the STO circuit. The drive generates an indication if one is defined for the 'stopped'
state in parameter 31.22 (see the firmware manual).
• Give a start command to verify that the STO function blocks the drive's operation. The motor
should not start.
• Close the STO circuit.
• Reset any active faults. Restart the drive and check that the motor runs normally.
The Safe torque off function 229
Содержание ACS580-04
Страница 1: ... ABB GENERAL PURPOSE DRIVES ACS580 04 drive modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 26: ...26 ...
Страница 60: ...60 ...
Страница 69: ...2 1 Tapping screw M6 12 Torx T30 Hex 9 N m 6 6 lbf ft Mechanical installation 69 10 ...
Страница 72: ...72 ...
Страница 100: ...100 ...
Страница 120: ...120 ...
Страница 128: ...2 7a 7b 5 3 3 7a 7b 8a 8b 8b 4 128 Installation example with full cabling panels option H381 ...
Страница 133: ...Installation example with full cabling panels option H381 133 ...
Страница 134: ...134 ...
Страница 146: ...146 ...
Страница 157: ...External control unit option P906 157 ...
Страница 158: ...Dimension drawing The dimensions are in millimeters and inches 158 External control unit option P906 ...
Страница 162: ...162 ...
Страница 164: ...164 ...
Страница 200: ...R10 standard configuration 200 Dimension drawings ...
Страница 201: ...R10 with options E208 0H354 H356 H370 0H371 Dimension drawings 201 ...
Страница 202: ...R10 with option B051 202 Dimension drawings ...
Страница 203: ...R10 with options E208 H356 P906 Dimension drawings 203 ...
Страница 204: ...R10 with options E208 0H371 H356 0H354 H370 P906 204 Dimension drawings ...
Страница 205: ...R10 with options B051 P906 Dimension drawings 205 ...
Страница 207: ...R10 Cabling panels H381 installed into a Rittal VX25 enclosure 3AXD50000439317 Dimension drawings 207 ...
Страница 208: ...R11 standard configuration 208 Dimension drawings ...
Страница 209: ...R11 with options E208 0H371 H356 0H354 H370 Dimension drawings 209 ...
Страница 210: ...R11 with option B051 210 Dimension drawings ...
Страница 211: ...R11 with options E208 H356 P906 Dimension drawings 211 ...
Страница 212: ...R11 with options E208 0H371 H356 0H354 H370 P906 212 Dimension drawings ...
Страница 213: ...R11 with options B051 P906 Dimension drawings 213 ...
Страница 215: ...R11 Cabling panels H381 installed into a Rittal VX25 enclosure 3AXD50000438938 Dimension drawings 215 ...
Страница 248: ...248 ...
Страница 254: ...Dimension drawings The dimensions are in millimeters 254 CAIO 01 bipolar analog I O adapter module ...
Страница 260: ...260 ...
Страница 265: ...CHDI 01 115 230 V digital input extension module 265 ...
Страница 266: ...266 ...
Страница 272: ...272 CMOD 01 multifunction extension module external 24 V AC DC and digital I O ...
Страница 278: ...278 ...
Страница 280: ...280 ...