Maintenance
After the operation of the circuit is validated at start-up, the STO function shall be
maintained by periodic proof testing. In high demand mode of operation, the maximum
proof test interval is 20 years. In low demand mode of operation, the maximum proof
test interval is 10 years; see section
. It is assumed that all
dangerous failures of the STO circuit are detected by the proof test. To perform the
proof test, do the
Validation test procedure (page 229)
Note: See also the Recommendation of Use CNB/M/11.050 (published by the European
co-ordination of Notified Bodies) concerning dual-channel safety-related systems
with electromechanical outputs:
•
When the safety integrity requirement for the safety function is SIL 3 or PL e (cat.
3 or 4), the proof test for the function must be performed at least every month.
•
When the safety integrity requirement for the safety function is SIL 2 (HFT = 1) or
PL d (cat. 3), the proof test for the function must be performed at least every 12
months.
The STO function of the drive does not contain any electromechanical components.
In addition to proof testing, it is a good practice to check the operation of the function
when other maintenance procedures are carried out on the machinery.
Include the Safe torque off operation test described above in the routine maintenance
program of the machinery that the drive runs.
If any wiring or component change is needed after start-up, or the parameters are
restored, do the test given in section
Validation test procedure (page 229)
.
Use only spare parts approved by ABB.
Record all maintenance and proof test activities in the machine logbook.
■
Competence
The maintenance and proof test activities of the safety function must be carried out
by a competent person with adequate expertise and knowledge of the safety function
as well as functional safety, as required by IEC 61508-1 clause 6.
The Safe torque off function 233
Содержание ACS580-04
Страница 1: ... ABB GENERAL PURPOSE DRIVES ACS580 04 drive modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 26: ...26 ...
Страница 60: ...60 ...
Страница 69: ...2 1 Tapping screw M6 12 Torx T30 Hex 9 N m 6 6 lbf ft Mechanical installation 69 10 ...
Страница 72: ...72 ...
Страница 100: ...100 ...
Страница 120: ...120 ...
Страница 128: ...2 7a 7b 5 3 3 7a 7b 8a 8b 8b 4 128 Installation example with full cabling panels option H381 ...
Страница 133: ...Installation example with full cabling panels option H381 133 ...
Страница 134: ...134 ...
Страница 146: ...146 ...
Страница 157: ...External control unit option P906 157 ...
Страница 158: ...Dimension drawing The dimensions are in millimeters and inches 158 External control unit option P906 ...
Страница 162: ...162 ...
Страница 164: ...164 ...
Страница 200: ...R10 standard configuration 200 Dimension drawings ...
Страница 201: ...R10 with options E208 0H354 H356 H370 0H371 Dimension drawings 201 ...
Страница 202: ...R10 with option B051 202 Dimension drawings ...
Страница 203: ...R10 with options E208 H356 P906 Dimension drawings 203 ...
Страница 204: ...R10 with options E208 0H371 H356 0H354 H370 P906 204 Dimension drawings ...
Страница 205: ...R10 with options B051 P906 Dimension drawings 205 ...
Страница 207: ...R10 Cabling panels H381 installed into a Rittal VX25 enclosure 3AXD50000439317 Dimension drawings 207 ...
Страница 208: ...R11 standard configuration 208 Dimension drawings ...
Страница 209: ...R11 with options E208 0H371 H356 0H354 H370 Dimension drawings 209 ...
Страница 210: ...R11 with option B051 210 Dimension drawings ...
Страница 211: ...R11 with options E208 H356 P906 Dimension drawings 211 ...
Страница 212: ...R11 with options E208 0H371 H356 0H354 H370 P906 212 Dimension drawings ...
Страница 213: ...R11 with options B051 P906 Dimension drawings 213 ...
Страница 215: ...R11 Cabling panels H381 installed into a Rittal VX25 enclosure 3AXD50000438938 Dimension drawings 215 ...
Страница 248: ...248 ...
Страница 254: ...Dimension drawings The dimensions are in millimeters 254 CAIO 01 bipolar analog I O adapter module ...
Страница 260: ...260 ...
Страница 265: ...CHDI 01 115 230 V digital input extension module 265 ...
Страница 266: ...266 ...
Страница 272: ...272 CMOD 01 multifunction extension module external 24 V AC DC and digital I O ...
Страница 278: ...278 ...
Страница 280: ...280 ...