Jumper J2 on the front of the drive = Modbus
J2: Comm. Mode
Modbus
•
Parameter 58.01 (protocol enable) = 1 (Modbus RTU)
Connecting a PC
To connect a PC to the drive, there are two alternatives:
•
Use an ACS-AP-I/S/W assistant control panel as a converter. Use a USB type
A – type Mini-B cable. The maximum permitted length of the cable is 3 m (9.8 ft).
•
Use a USB to RJ45 converter. You can order it from ABB (BCBL-01,
3AXD50000032449). Connect the cable to the Panel and PC tool port (RJ45).
For information on the Drive composer PC tool, refer to
Drive composer PC tool
user's manual (3AUA0000094606 [English]).
You can use the CCA-01 cold configuration tool to download software and change
drive parameters without connecting the drive to the input power. The CCA-01
does not operate if the drive is powered.
Electrical installation 75