Electrical installation
Measuring the insulation
See the electrical installation instructions of the drive.
Connecting power cables
See the electrical installation instructions of the drive.
Connection the control cables
Connect the thermal switch of the brake resistor as described in
system against thermal overload (page 139)
.
Start-up
Set the following parameters:
1.
Disable the overvoltage control of the drive with parameter
30.30 Overvoltage
control.
2.
Set the source of parameter
31.01 External event 1 source to point to the digital
input where the thermal switch of the brake resistor is wired.
3.
Set parameter
31.02 External event 1 type to Fault.
4. Enable the brake chopper by parameter
43.06 Brake chopper enable. If Enabled
with thermal model is selected, set also the brake resistor overload protection
parameters
43.08 and 43.09 according to the application.
5. Check the resistance value of parameter
43.10 Brake resistance.
With these parameter settings, the drive generates a fault and coasts to a stop
on brake resistor overtemperature.
Resistor braking 141
Содержание ACS180
Страница 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 12: ...12...
Страница 36: ...36...
Страница 41: ...4 Tighten the mounting screws Mechanical installation 41...
Страница 58: ...58...
Страница 76: ...76...
Страница 90: ...90...
Страница 130: ...Frame R0 130 Dimension drawings...
Страница 131: ...Frame R1 Dimension drawings 131...
Страница 133: ...Frame R3 Dimension drawings 133...
Страница 134: ...Frame R4 134 Dimension drawings...
Страница 142: ...142...
Страница 162: ...Declarations of conformity 162 The Safe torque off function...
Страница 163: ...The Safe torque off function 163...
Страница 164: ...164 The Safe torque off function...
Страница 165: ...The Safe torque off function 165...
Страница 166: ...166...