Default I/O connection diagram (ABB standard macro)
Description
Term.
1)
Connection
Digital I/O
21
22
8
9
10
11
12
18
19
20
5
6
7
1
2
3
4
25
26
27
28
J1
J2
14
13
15
16
17
23
24
Aux. +24 V DC, max 200 mA
24 V
Aux. voltage output common
DGND
Stop (0) / Start (1)
DI1
Forward (0) / Reverse (1)
DI2
Constant speed selection
DI3
Constant speed selection
DI4
Digital input common
DCOM
Running
DO
Digital output common
DO COM
Digital output auxiliary voltage
DO SRC
Analog I/O
Speed reference (0…10V)
AI1/DI5
Analog input circuit common
AGND
Not used
AI2
Analog output circuit common
AGND
Output frequency (0...20mA)
AO
Ref. v10 V DC
10V
Signal cable shield (screen)
SCREEN
Safe torque off (STO)(only on ACS180-04S)
Safe torque off function.
Connected at the factory. Drive
starts only when both circuits
are closed.
S+
SGND
S1
S2
Relay output
No fault [Fault (-1)]
NC
COM
NO
EIA-485 Modbus RTU
Embedded Modbus RTU (EIA-
485)
B+
A-
AGND
SHIELD
Jumper
Modbus termination selection
Termination
Communication mode selection
Comm.Mode
1) Terminal size: 0.5 mm² … 1 mm²
Electrical installation 69
Содержание ACS180
Страница 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 12: ...12...
Страница 36: ...36...
Страница 41: ...4 Tighten the mounting screws Mechanical installation 41...
Страница 58: ...58...
Страница 76: ...76...
Страница 90: ...90...
Страница 130: ...Frame R0 130 Dimension drawings...
Страница 131: ...Frame R1 Dimension drawings 131...
Страница 133: ...Frame R3 Dimension drawings 133...
Страница 134: ...Frame R4 134 Dimension drawings...
Страница 142: ...142...
Страница 162: ...Declarations of conformity 162 The Safe torque off function...
Страница 163: ...The Safe torque off function 163...
Страница 164: ...164 The Safe torque off function...
Страница 165: ...The Safe torque off function 165...
Страница 166: ...166...