Planning the cabinet installation
23
Planning the cabinet installation
What this chapter contains
This chapter guides in planning the installation of a converter module into a user-
defined cabinet. The chapter gives free space requirements around the module for
cooling, cabinet cooling data and layout examples. The issues discussed are
essential for the safe and trouble-free use of the drive system.
Note:
The installation must always be designed and made according to applicable
local laws and regulations. ABB does not assume any liability whatsoever for any
installation which breaches the local laws and/or other regulations.
Cabinet construction
The cabinet frame must be sturdy enough to carry the weight of the drive
components, control circuitry and other equipment installed in it.
The cabinet must protect the converter module against contact and meet the
requirements for dust and humidity, see chapter
Technical data
in
ACS800-04/04M/
U4 Hardware Manual
[3AFE64671006 (English)].
Disposition of the devices
For easy installation and maintenance, a spacious layout is recommended. Sufficient
cooling air flow, obligatory clearances, cables and cable support structures all
require space.
The control boards must not be installed near main circuits or hot parts.
The following sections show a few layout examples. For example layouts in
Rittal TS 8 cabinet, refer to
ACS800-04/U4 Rittal TS 8 Cabinet Installation
[3AFE68372330 (English)].
Содержание ACS 800 Series
Страница 4: ......
Страница 10: ...Table of contents 10...
Страница 119: ...Dimensional drawings 119 Dimensional drawings...
Страница 120: ...Dimensional drawings 120 Frame size R7 without pedestal mm 64796003_3 7 E Center of gravity...
Страница 121: ...Dimensional drawings 121 Frame size R7 with bottom exit mm 64796003_6 7 G...
Страница 122: ...Dimensional drawings 122 Frame size R7 with bottom exit and top entry and bottom exit shrouds mm 64796003_7 7 E...
Страница 123: ...Dimensional drawings 123 Frame size R7 with busbars on the left side mm 64796003_5 7 G...
Страница 125: ...Dimensional drawings 125 Frame size R7 pedestal busbars on the long side mm 64796003_4 7 E Bilateral output busbar...
Страница 127: ...Dimensional drawings 127 Frame size R8 without pedestal mm 64801082_3 6 E Center of gravity...
Страница 128: ...Dimensional drawings 128 Frame size R8 with busbars on the left side mm 64801082_5 6 E...
Страница 129: ...Dimensional drawings 129 Frame size R8 with top entry and vertical busbar shrouds mm 64801082_6 6 E...
Страница 131: ...Dimensional drawings 131 Frame size R8 pedestal busbars on the long side mm 64801082_4 6 E Bilateral output busbar...
Страница 136: ...Dimensional drawings 136 Control Panel Holder RPMP 21 J413 64770306_20 20 E...
Страница 137: ...Dimensional drawings 137 Drive Control Unit RDCU 02 64675214 B Can be mounted on a DIN rail EN 50022 35 mm x 7 5 mm...
Страница 138: ...Dimensional drawings 138 Dimensional drawings USA...
Страница 139: ...Dimensional drawings 139 Frame size R7 without pedestal inches 68439221_3 7 A 64796003 asm E Center of gravity...
Страница 140: ...Dimensional drawings 140 Frame size R7 with bottom exit inches 68439221_6 7 F F F...
Страница 142: ...Dimensional drawings 142 Frame size R7 with busbars on the left side inches 68439221_5 7 F...
Страница 146: ...Dimensional drawings 146 Frame size R8 without pedestal inches 68440513_3 6 A 64801082 asm E Center of gravity...
Страница 147: ...Dimensional drawings 147 Frame size R8 with busbars on the left side inches 68440513_5 6 A 64801082 asm E...
Страница 148: ...Dimensional drawings 148 Frame size R8 with top entry and vertical busbar shrouds inches 68440513_6 6 A 64801082 asm E...
Страница 152: ...Dimensional drawings 152...
Страница 154: ...Circuit diagrams 154 00362825 B ACS800 04 04M drive module Components to be provided and wired by the user Safety relay...
Страница 160: ...Assembly drawings 160...
Страница 161: ......