Appendix A – ACS/ACC/ACP 604/607 Technical Data
A-30
ACx=ACS/ACC/ACP
ACS/ACC/ACP 604/607 Drives
UL/CSA Markings
The UL/UL
C
/CSA markings of the ACS 600 drives are listed below (x).
1)
the approval is valid up to 600 V
UL
ACS 600 is suitable for use in a circuit capable of delivering not more than 65 kA rms
symmetrical amperes at 480 V maximum (500 V units), and at 600 V maximum (690 V
units).
ACS 600 provides overload protection in accordance with the National Electrical Code
(US). See
ACS 600 Firmware Manual for setting. Default setting is off, must be
activated at start-up.
ACS 600 drives are to be used in a heated indoor controlled environment. See
subsection
Ambient Conditions for specific limits.
ACS 600 brake chopper - ABB has brake chopper modules that, when applied with
appropriately sized braking resistors, will allow the drive to dissipate regenerative
energy (normally associated with quickly decelerating a motor). Proper application of
the brake chopper is defined in the Brake Chopper Installation Manual (NBRA-6xx;
Braking Choppers Installation and Start Up Guide), Appendix A. These guide lines will
allow you to size brake choppers to your specific application needs for standard or
extended duty cycles. This can be applied to a single drive or multiple drives with DC
Bus connected to allow a sharing of regenerative energy.
ACx 600 Type
UL
UL
C
CSA
ACS 601 (IP 22)
400 V, 500 V and 600
1)
V ranges
x
x
x
ACs 601 (IP 54)
x
x
pending
ACS 604 frame sizes R7 to R9
400 V, 500 V and 600
1)
V ranges
x
x
x
ACS 604
600 V parallel connected units
pending
pending
pending
Содержание ACS 600 Series
Страница 2: ......
Страница 4: ......
Страница 16: ...xiv ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 20: ...Chapter 1 Introduction 1 4 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 38: ...Chapter 5 Maintenance 5 2 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 72: ...Appendix B ACx 607 Dimensional Drawings B 2 ACx ACX ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 81: ......