Chapter 8 – Parameters
8-16
ACA 635 IGBT Supply Sections
21 Start/Stop
Functions
Code Parameter
T
y
p
e
Default
Range/Unit
Description
21
START/STOP
21.01
DC LEVEL START B NO
(0)
NO
Disable level start
(1)
YES
Enable level start.
Note:
If Par. 99.08 AUTO LINE ID
RUN is set to YES, the ACA 635 performs the ID Run
in NAMC board power-up and modulates for one
second thereafter. The ACA 635 stops and waits until
DC voltage exceeds the level of Par. 21.02 DC
VOLTAGE LEVEL.
21.02
DC VOLTAGE
LEVEL
R See table
below.
See table below.
Intermediate circuit DC voltage level at which the
modulation starts
21.03
STOP LEVEL
TIME
R 1000 ms
ms
Modulator is stopped when the power is higher than
defined with Par. 21.04 STOP LEVEL POWER for a
time defined with this parameter.
21.04
STOP LEVEL
POWER
R 0 kW
kW
Motoring power to stop the modulator
Par. 4.04 CONV
NOM VOLTAGE
(V)
Default of Par. 21.02:
1.1
×
Ö
2
×
Par. 4.04 CONV
NOM VOLTAGE
Range of Par. 21.02:
(65% ...120%)
×
Ö
2
×
Par. 4.04 CONV
NOM VOLTAGE
(V)
Minimum (V)
Maximum (V)
415
646
380
706
500
778
457
851
690
1073
632
1174
Содержание ACS 600 MultiDrive
Страница 4: ......
Страница 8: ...Safety Instructions vi ACA 635 IGBT Supply Sections ...
Страница 57: ...Chapter 7 Fault Tracing 7 8 ACA 635 IGBT Supply Sections ...
Страница 99: ...Appendix B Circuit Diagrams B 2 ACA 635 IGBT Supply Sections H ...
Страница 100: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 3 ...
Страница 101: ...Appendix B Circuit Diagrams B 4 ACA 635 IGBT Supply Sections ...
Страница 102: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 5 ...
Страница 103: ...Appendix B Circuit Diagrams B 6 ACA 635 IGBT Supply Sections ...
Страница 104: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 7 ...
Страница 105: ...Appendix B Circuit Diagrams B 8 ACA 635 IGBT Supply Sections ...
Страница 106: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 9 ...
Страница 107: ...Appendix B Circuit Diagrams B 10 ACA 635 IGBT Supply Sections ...
Страница 108: ......