Chapter 8 – Parameters
8-20
ACA 635 IGBT Supply Sections
51 Communication
Module
70 DDCS Control
30.12 DC
UNDERVOLT
TRIP
R 293/354/488
0...747 VDC
(415 V units)
0...900 VDC
(500 V units)
0...1242 V DC
(690 V units)
Intermediate circuit DC undervoltage trip limit.
The higher range limit is determined by Par.
30.11 DC OVERVOLT TRIP. When the setting
of this parameter is changed, the
corresponding lower range limit of Par. 30.11
DC OVERVOLT TRIP will also change. This
parameter also determines DC voltage check
limit during charging.
1 = 1
Code Parameter
T
y
p
e
Description
51
COMMUNICATION
MODULE
This group defines the communication parameters for a fieldbus adapter module. The
parameter names are copied from the module when it is installed and its connection to the
drive is activated with Parameter 98.02 COMM MODULE. See the module manual.
51.01
FIELDBUS PAR1
C
Module type and software version
51.02
...
51.15
FIELDBUS_PAR2
...15
R
According to module type
Code Parameter
T
y
p
e
Default
Alternative Settings
( ) Fieldbus Equivalent
Description
Integer
Scaling
70
DDCS CONTROL
70.01
CH0 NODE ADDR
R
1
1...125
Node address for channel CH0. When
using the AC 80 system, the address must
be 1. In other control systems, node
address is set according to the
application.
1 = 1
70.02
CH0 LINK
CONTROL
R
10
1...15
DDCS channel CH0 intensity control for
transmission LEDs. This parameter can
be used in special cases to optimise the
communication performance in the link.
1= 1
70.03
CH0 BAUD RATE
I
4 Mbit/s
(0)
8 Mbit/s (not in use);
(1)
4 Mbit/s;
(2)
2 Mbit/s (not in use);
(3)
1 Mbit/s
Channel CH0 communication speed. This
parameter must be set to 4 Mbits/s, when
FCI communication module is used.
Otherwise overriding system
automatically sets the communication
speed.
70.04
CH0 TIMEOUT
R
100 ms
0...60000 ms
The delay time before a communication
break fault is indicated. The time count
starts when the link does not update the
message. During the time elapsing, CH0
TIMEOUT warning is set by 9.12 SUPPLY
ALARM WORD bit 0. When the value of
Par. 70.04 is zero, timeout is not
monitored and CH0 COM LOST fault is
not indicated regardless of the value of
Par. 70.05.
1 = 1 ms
Содержание ACS 600 MultiDrive
Страница 4: ......
Страница 8: ...Safety Instructions vi ACA 635 IGBT Supply Sections ...
Страница 57: ...Chapter 7 Fault Tracing 7 8 ACA 635 IGBT Supply Sections ...
Страница 99: ...Appendix B Circuit Diagrams B 2 ACA 635 IGBT Supply Sections H ...
Страница 100: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 3 ...
Страница 101: ...Appendix B Circuit Diagrams B 4 ACA 635 IGBT Supply Sections ...
Страница 102: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 5 ...
Страница 103: ...Appendix B Circuit Diagrams B 6 ACA 635 IGBT Supply Sections ...
Страница 104: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 7 ...
Страница 105: ...Appendix B Circuit Diagrams B 8 ACA 635 IGBT Supply Sections ...
Страница 106: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 9 ...
Страница 107: ...Appendix B Circuit Diagrams B 10 ACA 635 IGBT Supply Sections ...
Страница 108: ......