![ABB ACQ580-34 Скачать руководство пользователя страница 173](http://html.mh-extra.com/html/abb/acq580-34/acq580-34_hardware-manual_2546173.webp)
Power cables
The table below gives typical copper and aluminum cable types with concentric copper
shield for the drives with nominal current. The value separated by the plus sign means the
diameter of the PE conductor. See also section
Terminal and entry data for the power
UL (NEC)
2)
IEC
1)
Drive type
ACQ580-34-
Cu cable type
Al cable type
Cu cable type
AWG/kcmil
mm
2
mm
2
U
n
= 400 V, 480 V (IEC)
2 × 2/0
2 × (3 × 95)
2 × (3 × 70 + 35)
246A-4
2 × 3/0
2 × (3 × 150)
2 × (3 × 95 + 50)
293A-4
2 × 250 MCM
2 × (3 × 185)
2 × (3 × 120 + 70)
365A-4
2 × 400 MCM
2 × (3 × 240)
2 × (3 × 150 + 70)
442A-4
2 × 500 MCM or 3 × 250 MCM
3 × (3 × 150)
3 × (3 × 95 + 50)
505A-4
2 × 600 MCM or 3 × 300 MCM
3 × (3 × 185)
3 × (3 × 120 + 70)
585A-4
2 × 700 MCM or 3 × 350 MCM
3 × (3 × 240)
3 × (3 × 150 + 70)
650A-4
U
n
= 480 V, UL (NEC)
2 × 2/0
2 × (3 × 95)
2 × (3 × 70 + 35)
240A-4
2 × 4/0
2 × (3 × 150)
2 × (3 × 95 + 50)
302A-4
2 × 250 MCM
2 × (3 × 185)
2 × (3 × 120 + 70)
361A-4
2 × 350 MCM
2 × (3 × 240)
2 × (3 × 150 + 70)
414A-4
2 × 500 MCM or 3 × 250 MCM
3 × (3 × 150)
3 × (3 × 95 + 50)
477A-4
3AXD00000586175
The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F)
(EN 60204-1 and IEC 60364-5-52). For other conditions, dimension the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
1)
The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth
(directly buried). For other conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
2)
Temperature:
For IEC, select a cable rated for at least 70 °C maximum permissible temperature of conductor
in continuous use. For North America, power cables must be rated for 75 °C (167 °F) or higher.
Voltage:
600 V AC cable is accepted for up to 500 V AC.
Terminal data for the control cables
See section
.
Technical data 173
Содержание ACQ580-34
Страница 1: ... ABB DRIVES FOR WATER ACQ580 34 drive modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 14: ...14 ...
Страница 24: ...24 ...
Страница 50: ...50 ...
Страница 60: ...60 ...
Страница 70: ...70 ...
Страница 94: ...94 ...
Страница 110: ...110 ...
Страница 122: ...122 ...
Страница 132: ...Dimension drawing 132 External control unit option P906 ...
Страница 140: ...140 ...
Страница 144: ...144 ...
Страница 164: ...164 ...
Страница 184: ...Standard configuration E208 and E210 included 184 Dimension drawings ...
Страница 185: ...Drive module with option B051 Dimension drawings 185 ...
Страница 186: ...Drive module with options B051 H370 186 Dimension drawings ...
Страница 187: ...LCL filter module Dimension drawings 187 ...
Страница 190: ...190 ...
Страница 208: ... Declaration of conformity 208 The Safe torque off function ...
Страница 214: ...214 ...
Страница 226: ...226 ...