CI873 Connections
Section 2 Functional Description
32
9ARD000014-600 A
For example, in case of LD 800DN linking device, where T -> O RPI is set to 10ms.
The time out multiplier is preset at 2 (not configurable by user). The Time Out value
is derived from the following formula:
Time Out value = T -> O RPI * Time Out Multiplier = 40ms.
So, if the CI873 EtherNet/IP I/O scanner does not receive any packets from LD
800DN for a period defined by the Time Out Value (here, 40ms) then the Implicit
messaging connection to LD 800DN times out and no I/O data from DeviceNet
slaves are updated to IEC 1131 application, but instead will have ISP values.
Connection Time-out Multiplier
The Connection Time-out Multiplier specifies the multiplier applied to the RPI to
obtain the connection time-out value. Devices shall stop transmitting on a
connection whenever the connection times out even if the pending close has been
sent. The multiplier shall be as represented in the below
.
Table 1. Connection Time-out Multiplier Values
Value
Multiplier
0
x4
1
x8
2
x16
3
x32
4
x64
5
x128
6
x256
7
x512
Содержание AC 800M
Страница 2: ......
Страница 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Страница 10: ...Table of Contents 10 9ARD000014 600 A ...
Страница 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Страница 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Страница 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Страница 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Страница 59: ...Figure 13 Device Tab for Non Modular Section 3 Device Import Wizard Device 9ARD000014 600 A 59 ...
Страница 60: ...Figure 14 Device tab for Modular I O Device Section 3 Device Import Wizard 60 9ARD000014 600 A ...
Страница 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Страница 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Страница 134: ...Figure 55 Inserted EtherNet IP Device Inserting EtherNet IP Device unit Section 4 Configuration 134 9ARD000014 600 A ...
Страница 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Страница 259: ......