Section 4 Configuration
Configuring S200 I/O Modules
9ARD000014-600 A
157
Ctrl Out 0
Bits 06-08
Calibration Control bits
- bits 06. 07 and 08
06
Enable bit
- When this bit is set (1), the counter can be
calibrated
07
Direction bit
- When this bit is set (1), calibration is
performed in a negative direction; when reset (0),
calibration is performed in a positive direction.
08
Reset bit
- Calibration is acknowledged and a new
calibration is enabled on a positive edge on this bit.
Bits 09-10 10
09
Gate Control bits
0
0
No gate function on input G
0
1
Counting only if G is high (active)
1
0
Counting only if G is low (inactive)
1
1
The counter can be calibrated when G is high
(active)
Bits 11-12 12
11
Store Control bits
- These bits will trigger a Store
only if the channel Store status bit (L0 or L1) is
cleared (0).
0
0
Save the counter value on the positive edge of Z (if
StoredX= O)
0
1
Save the counter value on the positive edge of G (if
StoredX= O)
1
0
Save the counter value on the negative edge of G (if
StoredX= O)
1
1
Save the counter value on the positive edge and
negative edge of G (if Stored X = 0)
Bit 13
Rollover bit
- When set (1), the counter counts up to the preset
and then restarts at 0. If this bit is reset (0) (not rollover), the
rollover preset value = FFFF (hex = 65535 (decimal).
Table 27. Description of Channels for 200-IP2 (Continued)
Channel Name
Bit
Definition
Содержание AC 800M
Страница 2: ......
Страница 3: ...AC 800M EtherNet IP DeviceNet Configuration System Version 6 0 ...
Страница 10: ...Table of Contents 10 9ARD000014 600 A ...
Страница 18: ...Released User Manuals and Release Notes About This User Manual 18 9ARD000014 600 A ...
Страница 22: ...Figure 1 System configuration Device Import Wizard Section 1 Introduction 22 9ARD000014 600 A ...
Страница 26: ...Linear Network Section 1 Introduction 26 9ARD000014 600 A ...
Страница 46: ...Hot Swap of EtherNet IP Device Section 2 Functional Description 46 9ARD000014 600 A ...
Страница 59: ...Figure 13 Device Tab for Non Modular Section 3 Device Import Wizard Device 9ARD000014 600 A 59 ...
Страница 60: ...Figure 14 Device tab for Modular I O Device Section 3 Device Import Wizard 60 9ARD000014 600 A ...
Страница 68: ...Figure 22 Enum Values File Section 3 Device Import Wizard 68 9ARD000014 600 A ...
Страница 71: ...Section 3 Device Import Wizard File 9ARD000014 600 A 71 Figure 25 EDS Range selection ...
Страница 134: ...Figure 55 Inserted EtherNet IP Device Inserting EtherNet IP Device unit Section 4 Configuration 134 9ARD000014 600 A ...
Страница 222: ...Auxiliary RS 232 9 Pin D Subminiature Section 8 Hardware Connections 222 9ARD000014 600 A ...
Страница 259: ......