Technical specifications
Page 3-10
ABB Control - AC 31
1SBC 260400 R1001-b
06.99
40 series
50series
07 CR 41
24 V d.c.
07 CT 41
24 V d.c.
07 CR 41
120/230 V a.c.
07 KR 51
24 V d.c.
07 KT 51
24 V d.c.
07 KR 51
120/230 V a.c.
- Weight
400 g
800 g
400 g
800 g
Power supply
- Power supply voltage:
Nominal value
Admissible range
24 V d.c.
19.2 to 30 V
120 / 230 V a.c.
97.75 to
126.5 V or
195.5 to 253 V
24 V d.c.
19.2 à 30 V
120 / 230 V a.c.
97.75 to
126.5 V or
195.5 to 253 V
- Consumption:
central unit alone typical.
Maximum configuration typical.
120 mA
400 mA
30 mA
100 mA
120 mA
400 mA
30 mA
100 mA
- Polarity reversal protection
yes
no
yes
no
- 24 V d.c. isolated power for the
inputs:
Voltage range
Output current
Short circuit protection
no
-
-
-
yes
19.2 to 30 V
400 mA
yes
no
-
-
-
yes
19.2 to 30 V
400 mA
yes
- Dissipation
5 W (6 W for 07 CT 41)
10 W
5 W (6 W for 07 KT 51)
10 W
Incorporated binary inputs
- Number of inputs
8
8
8
8
8
8
- Isolation of inputs / electronic
1500 V a.c.
1500 V a.c.
1500 V a.c.
1500 V a.c.
1500 V a.c.
1500 V a.c.
- Input types
PNP and
NPN
PNP and
NPN
PNP and
NPN
PNP and
NPN
PNP and
NPN
PNP and
NPN
- Input voltage:
Nominal value
Signal at 0 (IEC 1131-2)
Signal at 1 (IEC 1131-2)
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
- Input current at 24 V d.c.:
Inputs I62.02 to I62.07
Inputs I62.00 and I62.01
7 mA
9 mA
7 mA
9 mA
7 mA
9 mA
7 mA
9 mA
7 mA
9 mA
7 mA
9 mA
- Filtering time:
Standard input
Input with counter configuration
Input with interruption
configuration
5 ms
70
µ
s
90
µ
s
5 ms
70
µ
s
90
µ
s
5 ms
70
µ
s
90
µ
s
5 ms
70
µ
s
90
µ
s
5 ms
70
µ
s
90
µ
s
5 ms
70
µ
s
90
µ
s
- Cable length:
Unshielded (not for the high
speed counter inputs)
Shielded
Non standard inputs
300 m
500 m
50 m
300 m
500 m
50 m
300 m
500 m
50 m
300 m
500 m
50 m
300 m
500 m
50 m
300 m
500 m
50 m
Содержание AC 31
Страница 1: ...Technical Manual Advant Controller 31 40 50 Series 1SBC 260400 R 1001 b ...
Страница 7: ......
Страница 28: ...AC 31 technical documentation ABB Control AC 31 Page 2 1 1SBC 260400 R1001 b 06 99 Chapter 2 Getting started ...
Страница 43: ......
Страница 45: ...Technical specifications Page 3 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Страница 83: ......
Страница 84: ...AC 31 technical documentation ABB Control AC 31 Page 4 1 1SBC 260400 R1001 b 06 99 Chapter 4 Installation ...
Страница 85: ...Installation Page 4 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Страница 109: ......
Страница 110: ...AC 31 technical documentation ABB Control AC 31 Page 5 1 1SBC 260400 R1001 b 06 99 Chapter 5 Programming ...
Страница 130: ...Programming ABB Control AC 31 Page 5 21 1SBC 260400 R1001 b 06 99 ...
Страница 141: ...Programming Page 5 32 ABB Control AC 31 1SBC 260400 R1001 b 06 99 Figure 5 10 Duplicating inputs of a function block ...
Страница 154: ...AC 31 technical documentation ABB Control AC 31 Page 6 1 1SBC 260400 R1001 b 06 99 Chapter 6 Program Optimization ...
Страница 172: ...AC 31 technical documentation ABB Control AC 31 Page 7 1 1SBC 260400 R1001 b 06 99 Chapter 7 Communication ...
Страница 182: ...Communication ABB Control AC 31 Page 7 11 1SBC 260400 R1001 b 06 99 ...
Страница 189: ......
Страница 190: ...AC 31 technical documentation ABB Control AC 31 Page 8 1 1SBC 260400 R1001 b 06 99 Chapter 8 Diagnosis ...
Страница 191: ...Diagnosis Page 8 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 Figure 8 1 Error detection LEDs ...
Страница 195: ...Diagnosis Page 8 6 ABB Control AC 31 1SBC 260400 R1001 b 06 99 Figure 8 2 AC31GRAF status window ...
Страница 203: ......
Страница 204: ...AC 31 technical documentation ABB Control AC 31 Annexes Page 1 1SBC 260400 R1001 b 06 99 Annexes ...
Страница 217: ......
Страница 218: ...AC 31 technical documentation ABB Control AC 31 Index Page 1 1SBC 260400 R1001 b 06 99 Index ...