Commissioning
Product manual 2CKA001473B5285
│
31
■
Heating mode
For operating a heat-based automatic single-room control. The temperature is regulated to
the setpoint value defined in the parameter.
■
Cooling mode
For operating a cooling-based automatic single-room control. The temperature is regulated
to the setpoint value defined in the parameter.
■
Additional heating stage
In addition to the control function described under heating, the additional stage enables the
activation of an additional heating circuit. This type of additional stage is used, for example,
to quickly heat up a bathroom with floor heating via a heated towel rack.
■
Additional cooling stage
In addition to the control function described under cooling, the additional stage enables the
activation of an additional cooling device. This type of additional stage is used, for example,
to quickly cool a room via an added cooling device.
■
Push-button
Triggering or switching over of operating modes with a button operation, for example
■
Central heating actuator
Central heating actuator installation with rail-mounting actuators in the sub-distribution.
■
Central cooling actuator
Central cooling actuator installation with rail-mounting actuators in the sub-distribution.
■
Two-point heating controller
The controller switches on when the room temperature exceeds the preconfigured threshold
value and remains active until the heating requirement drops below the preconfigured
bottom threshold value again.
■
Two-point cooling controller
The controller switches on when the room temperature exceeds the preconfigured threshold
value and remains active until the cooling requirement drops below the preconfigured
bottom threshold value again.
■
Automatic heating/cooling mode
This function is used for 2-pipe heating/cooling systems.
A switchover between heating and cooling mode of the device can be made automatically
over the whole system via a linked binary input, e.g. for four busbar systems that permit the
switchover between heating and cooling at all times. The device switches automatically
between heating and cooling and to the associated setpoint.
■
Two-point heating/cooling controller
The controller switches on when the room temperature exceeds or drops below the
preconfigured threshold value and remains active until the cooling/heating requirement
exceeds/drops below the preconfigured bottom threshold value again.