9 Based on Irms and Ip resolution.
When making adjustments, attempting to set the PLANT HI VOLTS setpoint below the PLANT LOW
VOLT setpoint will cause an error condition.
Table 8 Setpoint Resolution
NAME
DECIMAL PLACES
RESOLUTION
UNITS
Output True Power
0
10
INV MAX RMS I
(Output Eff. Current)
1
0.10
Aac
INV MAX PEAK I
(Output p
-
p Current)
1
0.20
Aac
INV HI CR FACT
(Crest Factor)
2
(0.03
@ nominal load)
None
Output Frequency
1
/
-
39m S
Hz
Inv Temp #1
0
1.0
°C
Inv Temp #2
0
1.0
°C
% OF CAPACITY
0
10
%
# REDUNDAND IMs
(# Redundant Inv)
0
1
None
# INVERTERS
↔
15 1 (As Shipped)
INV MAX PEAK I
↔
GL 28.0 A
ac
s
INV HI CR FACT
↔
GL 2.80 s
PLANT LO VOLTS
↔
15 100 V
ac
s
SHELF # (1 –
4) ↔
GL 1 s
% OF CAPACITY
←
15 80 % s
BATTERY LO VOLT
↔
15 44.0 V
dc
s
# REDUNDAND IMs
↔
15 1 s
INV MAX RMS I
→
GL 10.0 A
ac
s
PLANT HI VOLTS
↔
15 130 V
ac
s