Action
Test
Use a multimeter and insulating gloves.
Measure the input voltage to
the robot signal exchange
proxy.
Tip
For more details, see
Circuit
diagram - OmniCore C90XT
.
2
The input voltage should be 24 V.
Make sure that connector X1 is connected properly
on both ends.
•
If the input voltage is normal, proceed with
step
.
•
If the input voltage is abnormal, proceed with
step
.
•
If the controller is for CRB 15000, see
Troubleshooting the power unit on page 388
•
If the controller is not for CRB 15000, proceed
with step
Confirm that the controller is
for CRB 15000 or not.
3
•
If the connection is OK,
.
•
If there is a problem with the connection, re-
pair the connection and start over.
Check connection to the
power supply unit.
4
Use a multimeter and insulating gloves.
Measure the 24 V DC outputs
voltage.
5
The output voltage should be 24 V.
Make sure that connectors X2, X3, X4, X5, X17 and
X19 are connected properly on both ends.
•
If the output voltage is normal, proceed with
step
.
•
If the output voltage is abnormal, proceed with
step
The indicator LEDs are labelled AS1, AS2, ES1, ES2.
Check the indicator LEDs
AS1, AS2, ES1, ES2.
6
If the LEDs LED_AS1, AS2, ES1, ES2 are:
•
On (solid yellow), the robot signal exchange
proxy works well.
•
Off, either the robot signal exchange proxy is
faulty or it does not have sufficient input
voltage. Proceed with step
.
If the customer interface connectors are not well
connected to X14 and X15, the robot signal exchange
proxy cannot work normally.
•
If the connection is OK, proceed with step
.
•
If there is a problem with the connection, re-
pair the connection and go to step
Check that the customer inter-
face connectors are well con-
nected to X14 and X15.
Tip
For more details, see
Circuit
diagram - OmniCore C90XT
.
7
Use a multimeter and insulating gloves.
Check external safety ac-
cessories.
8
Measure the continuity in the connector. If there is
resistance, troubleshoot the external equipment.
Use a multimeter and insulating gloves.
Measure the AC OK signal.
9
The AC OK should be 0 V.
Make sure that connector X10 is connected properly
on both ends.
•
If the AC OK signal is 24 V, see
Troubleshooting the power unit on page 388
•
If the AC OK signal is 0 V, proceed with step
Continues on next page
418
Product manual - OmniCore C90XT
3HAC073706-001 Revision: E
© Copyright 2020-2021 ABB. All rights reserved.
7 Troubleshooting
7.3.12 Troubleshooting the robot signal exchange proxy
Continued
Содержание OmniCore C90XT
Страница 1: ...ROBOTICS Product manual OmniCore C90XT ...
Страница 2: ...Trace back information Workspace 21B version a6 Checked in 2021 05 31 Skribenta version 5 4 005 ...
Страница 36: ...This page is intentionally left blank ...
Страница 50: ...This page is intentionally left blank ...
Страница 360: ...This page is intentionally left blank ...
Страница 420: ...This page is intentionally left blank ...
Страница 428: ...This page is intentionally left blank ...
Страница 452: ...This page is intentionally left blank ...
Страница 456: ......
Страница 457: ......