HDD status LED
B
Status LED
C
Significance
Description
The power status LED indicates the status of the power supply and the
main computer hardware and firmware.
Power status, PC
PWR (green)
Normal behavior:
•
Off: During a normal startup the LED is off, until the COM Express
module inside the computer unit is started.
•
On solid: After completion of startup the LED is steady on.
Failure during startup (off between blinks). One to four short blinks, one
second off. This is repeated until power off.
•
Internal fail of power, FPGA, and/or the COM Express module.
•
Replace the computer unit.
Power failure during runtime (fast flashing between blinks). One to five
blinks, 20 fast flashing blinks. This is repeated until power off.
•
Temporary voltage drop, cycle the power to the controller.
•
Check the power supply voltage to the computer unit.
•
Replace the computer unit.
The disk status LED indicates access to the main computer persistent
memory.
Disk status, PC
HDD
Normal behavior:
•
No color at power on: R34 FPGA is loaded on the main board.
•
Yellow: Access (read/write) to internal mass memory.
The computer status LED indicates the startup progress of RobotWare
on the main computer.
Computer status,
PC STAT
(red/green)
Normal behavior:
1
Red, solid: Default when turning on the power.
2
Red, flashing: Initial self-test is ongoing and the operating system
is loading.
3
Green, even flashing (~1Hz): The operating system is loaded and
RobotWare is initializing.
4
Green, uneven flashing: The RobotWare system failed to load or
is not installed.
5
Green, solid: The computer is operational and the RobotWare
system is fully loaded.
If the LED does not turn steady green after approximately 5 minutes then
the LED can be used to identify the following issues:
•
No color: The internal power initialization failed. Restart the con-
troller. Replace the main computer if the problem remains.
•
Red, solid: Internal error. Restart the controller. Replace the main
computer if the problem remains.
•
Red, flashing continuously: Failed to load the operating system.
Restart the controller. See
Controller fails to start on page 380
Replace the main computer if the problem remains.
•
Green, even flashing continuously (~1Hz): Failure during start up.
Check error messages on FlexPendant. See
•
Green, uneven flashing: RobotWare Installation Utilities mode.
For information about the LEDs on the AnybusCC slave fieldbus adapter and the
PCIExpress master/slave fieldbus board, see the corresponding fieldbus manual.
Continues on next page
Product manual - OmniCore C90XT
405
3HAC073706-001 Revision: E
© Copyright 2020-2021 ABB. All rights reserved.
7 Troubleshooting
7.3.9 Troubleshooting the main computer
Continued
Содержание OmniCore C90XT
Страница 1: ...ROBOTICS Product manual OmniCore C90XT ...
Страница 2: ...Trace back information Workspace 21B version a6 Checked in 2021 05 31 Skribenta version 5 4 005 ...
Страница 36: ...This page is intentionally left blank ...
Страница 50: ...This page is intentionally left blank ...
Страница 360: ...This page is intentionally left blank ...
Страница 420: ...This page is intentionally left blank ...
Страница 428: ...This page is intentionally left blank ...
Страница 452: ...This page is intentionally left blank ...
Страница 456: ......
Страница 457: ......