This section defines the communication options for the Reader.
DeviceNet Network
AdaptaScan Readers support both DeviceNet Master/Slave and
Peer-to-Peer protocols.
On a DeviceNet Master/Slave network, Readers and other DeviceNet
slave devices communicate with a DeviceNet Scanner (Master). Up
to 63 slave devices are allowed on a master/slave network.
On a DeviceNet peer-to-peer network, up to 32 Readers can be
connected together. These Readers can:
•
work in a coordinated mode to read multiple bar code symbols on
different sides of the same package.
•
combine data from several Readers to a single Reader that
communicates the data to a host.
•
pass input and output status information between Readers.
Reader
Reader
Other
PLC-5 with 1771-SDN (DeviceNet Scanner)
DeviceNet Devices
AdaptaScan Bar Code Readers operate on a DeviceNet network at
the following baud rates (Kbps = Kilobits per Second):
Baud Rate
Supports Maximum Cable Length of:
125 Kbps
1640 feet (500 meters)
250 Kbps
656 feet (200 meters)
500 Kbps
328 feet (100 meters)
Communication Options