30 

at  32°F.  When  water  freezes  in  a  heat 
exchanger  significant  forces  are  exerted  on 
the components of the heat exchanger where 
the water is confined. 
 
Failure of the condenser due to freezing will 
allow  water  to  enter  the  refrigerant  circuit 
and  will  cause  extensive  damage  to  the 
refrigerant circuit components. Any damage 
to  the  equipment  as  a  result  of  water 
freezing  in  the  condenser  is  excluded  from 
coverage  under  AAON  warranties  and  the 
heat exchanger manufacturer warranties. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Unit  is  capable  of  operating  with  Entering 
Water Temperatures (EWT) as low as 57°F, 
during  the  cooling  mode,  without  the  need 
for  head  pressure  control.  If  the  EWT  is 
expected  to  be  lower  than  57°F  or  more 
stable  operation  is  desired,  a  factory 
provided  head  pressure  control  water  valve 
option is available. 
 
Glycol  solution  should  be  used  if  ambient 
temperatures  are  expected  to  fall  below 
freezing  or  if  the  loop  entering  water 
temperature  to  the unit  is  below 50°F while 
operating  in  the  heating  mode  (heat  pump 
units  only).  Adding  glycol  to  condenser 
water  causes  an  increase  in  pressure  drop 

and  also  results  in  a  decrease  in  unit 
performance.  A  minimum  concentration  of 
20% glycol solution is recommended. 
 

Table 2 - Glycol Freezing Points 

% Glycol 

Ethylene 

Glycol 

Propylene 

Glycol 

20 

18°F 

19°F 

30 

7°F 

9°F 

40 

-7°F 

-6°F 

50 

-28°F 

-27°F 

 
Water  loop  piping  runs  through  unheated 
areas  or  outside  the  building  should  be 
insulated. 
 

Water Piping 

Installing 

contractor 

must 

ensure 

differential  pressure  switch  or  water  flow 
switch  is  installed  between  the  condenser 
water  supply  and  return  connections.  This 
sensor  provides  a  signal  to  the  unit 
controller  that  water  flow  is  present  in  the 
refrigerant-to-water  heat  exchanger  and  the 
unit  can  operate  without  damaging  unit 
components. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 
 

 

WATER PRESSURE 

 
Prior  to  connection  of  condensing 
water supply, verify water pressure is 
less  than  maximum  pressure  shown 
on  unit  nameplate.  To  prevent  injury 
or  death  due  to  instantaneous 
release  of  high  pressure  water,  relief 
valves  should  be  field  supplied  on 
water 

piping. 

Supply 

water 

connection  may  require  a  backflow 
preventer  to  prevent  supply  makeup 
water from backing up into the public 
water system. 

    

 

WARNING

 

 
 

 

WATER FREEZING 

 
Failure  of  the  condenser  due  to 
freezing  will  allow  water  to  enter  the 
refrigerant  circuit  and  will  cause 
extensive  damage  to  the  refrigerant 
circuit  components.  Any  damage  to 
the  equipment  as  a  result  of  water 
freezing in the condenser is excluded 
from 

coverage 

under 

AAON 

warranties  and  the  heat  exchanger 
manufacturer warranties. 

    

 

WARNING

 

Содержание SA-028

Страница 1: ...loss of life FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WARNING WARNING QUALIFIED INSTALLER Improper installation...

Страница 2: ......

Страница 3: ...Heat Exchanger Cleaning 33 Electrical 33 Cutting Electrical Openings 34 Thermostat Control Wiring 35 Duct Connection 36 Condensate Drain Piping 36 Waterside Economizer 37 Hot Water Coil 41 Chilled Wat...

Страница 4: ...wnout Protection Module 51 Filter Replacement 53 Replacement Parts 54 AAON Warranty Service and Parts Department 54 Appendix A Heat Exchanger Corrosion Resistance 55 SA Series Startup Form 57 Maintena...

Страница 5: ...ails 22 Figure 5 One Piece Dual Unit Lifting Details 23 Figure 6 Two Piece Dual Unit Coil Section Lifting Details 24 Figure 7 Two Piece Dual Unit Fan Section Lifting Details 25 Figure 8 Dual unit with...

Страница 6: ...uld result in dangerous operation serious injury death or property damage Before servicing disconnect all electrical power to the unit More than one disconnect may be provided When servicing controls...

Страница 7: ...ng an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment PPE be worn should be followed WARNING UNIT HANDLING To prevent injury...

Страница 8: ...gen acetylene or air in place of refrigerant and dry nitrogen for leak testing A violent explosion may result causing injury or death WARNING Always use a pressure regulator valves and gauges to contr...

Страница 9: ...ooled condenser See Appendix A Heat Exchanger Corrosion Resistance for more information CAUTION OPEN LOOP APPLICATIONS Failure of the condenser as a result of chemical corrosion is excluded from cover...

Страница 10: ...unique to the model you have purchased 4 READ THE ENTIRE INSTALLATION OPERATION AND MAINTENANCE MANUAL OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL 5 Keep this manual and all...

Страница 11: ...on Protection F Option C Interior Corrosion Protection A1 Refrigerant Style 0 Air Handling Unit B R 410A Non Compressorized DX AHU E R 410A Variable Capacity Scroll Compressor A2 Unit Configuration 0...

Страница 12: ...nomizer 6 Row Coil 1B Plenum Height 0 33 Plenum Height A 37 Plenum Height B 41 Plenum Height C 45 Plenum Height D 49 Plenum Height E 53 Plenum Height F 57 Plenum Height G 37 Plenum Height Sound Attenu...

Страница 13: ...ved Plenum 5C Supply Air Blower Motor C 1 hp 1760 rpm D 2 hp 1760 rpm E 3 hp 1760 rpm F 5 hp 1760 rpm G 7 5 hp 1760 rpm H 10 hp 1760 rpm N 1 hp 1170 rpm P 2 hp 1170 rpm Q 3 hp 1170 rpm R 5 hp 1170 rpm...

Страница 14: ...hers 5 Field Installed DDC Controls by Others with Isolation Relays 6 Factory Installed DDC Controls Furnished by Others with Isolation Relays 14A Water Cooled Condenser 0 Standard None A Balancing Va...

Страница 15: ...ld Adjustable for Glycol 16 Interior Cabinet Options 0 Standard A Overflow Switch B UV Lights C Options A B 17 Blank 0 Standard 18 Blank 0 Standard 19 Code Options 0 Standard ETL U S A Listing D Chica...

Страница 16: ...odes All appliances must be electrically grounded in accordance with local codes or in the absence of local codes the current National Electric Code ANSI NFPA 70 or the current Canadian Electrical Cod...

Страница 17: ...at system switch to OFF or turn the unit off at the control panel and leave the unit off until the main power switch has been turned on again for at least 24 hours for units with compressor crankcase...

Страница 18: ...of condensate lines Waterside economizer coil units include a separate condensate drain pan which drains into the evaporator coil drain pan No additional drain line is needed for the waterside economi...

Страница 19: ...clearance requirements Allow adequate space for piping access and panel removal Condenser water piping and condensate drain connections are near the bottom on the back of the unit Figure 1 SA Series...

Страница 20: ...20 Figure 2 One Piece Single Unit Lifting Details...

Страница 21: ...21 Figure 3 Two Piece Single Unit Coil Section Lifting Details...

Страница 22: ...22 Figure 4 Two Piece Single Unit Fan Section Lifting Details...

Страница 23: ...23 Figure 5 One Piece Dual Unit Lifting Details...

Страница 24: ...24 Figure 6 Two Piece Dual Unit Coil Section Lifting Details...

Страница 25: ...25 Figure 7 Two Piece Dual Unit Fan Section Lifting Details...

Страница 26: ...plete unit A crow bar or similar tool can be used to line up the sections Factory provided bolts can then be used to secure the coil sections together See Figure 9 4 Align and set each fan section on...

Страница 27: ...27 Figure 8 Dual unit without splices and before being bolted together Figure 9 Dual Unit Assembly Details...

Страница 28: ...28 Figure 10 Dual unit with splices after being bolted together...

Страница 29: ...s Any damage to the equipment as a result of condenser failure from chemical corrosion due the fluid in the condenser is excluded from coverage under AAON warranties and the heat exchanger manufacture...

Страница 30: ...l solution is recommended Table 2 Glycol Freezing Points Glycol Ethylene Glycol Propylene Glycol 20 18 F 19 F 30 7 F 9 F 40 7 F 6 F 50 28 F 27 F Water loop piping runs through unheated areas or outsid...

Страница 31: ...ust be controlled All make up water has minerals in it and as the water is evaporated in the cooling tower these minerals remain As the mineral content of the water increases the conductivity of the w...

Страница 32: ...GPM PSI 45 4 2 45 4 2 45 4 2 45 1 7 39 3 3 39 3 3 39 3 3 39 35 2 8 35 2 8 35 2 8 35 SA 045 SA 050 SA 055 SA 058 GPM PSI GPM PSI GPM PSI GPM PSI 45 4 2 45 4 2 45 4 2 45 4 2 39 3 3 39 3 3 39 3 3 39 3 3...

Страница 33: ...t of unit specific wiring diagrams showing factory and field wiring are laminated in plastic and located inside the controls compartment door All units require field supplied electrical overcurrent an...

Страница 34: ...e that the metal skins of the foam part do not separate from the foam this would result in reduced structural integrity of the part Size supply conductors based on the unit Minimum Current Ampacity MC...

Страница 35: ...determine the allowable wiring distances Table 5 Control Wiring Wire Size Stranded Copper Conductors Only Total Wire Distance Allowable 20 AWG 200 ft 18 AWG 350 ft 16 AWG 500 ft 14 AWG 750 ft 12 AWG 1...

Страница 36: ...may be equipped with more than one condensate drain pan connection A p trap and drain line must be installed on every drain connection with the p trap not to exceed 6 from the drain connection The lin...

Страница 37: ...hanical cooling only During waterside economizer only mode of operation condenser water flows through the waterside economizer coil with modulating valves maintaining supply air temperature setpoint T...

Страница 38: ...s of factory provided piping assemblies Connect the piping assembly to the unit Connect the actuators to the water valves Actuators are factory wired and included inside the unit Installing contractor...

Страница 39: ...ight Intake Piping Kit Left Intake Piping Kit Assembly 6 Assembly 1 Assembly 2 Assembly 3 Assembly 4 Assembly 5 Waterside Economizer Valve Waterside Economizer Bypass Valve Head Pressure Control Valve...

Страница 40: ...zer Back View Right Intake Piping Kit Left Intake Piping Kit Assembly 6 Assembly 1 Assembly 2 Assembly 3 Assembly 4 Assembly 5 Waterside Economizer Valve Waterside Economizer Bypass Valve Head Pressur...

Страница 41: ...ks on the performance of the unit This includes checking of the air flow the air filters condenser water flow and refrigerant charge Supply Fans SA Series units are equipped with direct drive backward...

Страница 42: ...bolt and rotate the locking nut counter clockwise approximately four full rotations This will allow the locking nut to spin when the adjustment bolt is turned See Figure 17 Turn adjustment bolt count...

Страница 43: ...wheels or with VFDs Field airflow adjustment may be required at startup Air volume bands for the wheels are sized according to the unit s air delivery specifications and can also be ordered from the...

Страница 44: ...nd equipped with easy bend tabs that are to be inserted into pre punched slots provided on the wheel Once the band has been inserted into the slots it MUST BE secured by bending the tabs over from the...

Страница 45: ...proper charge After charging unit should be operated in cooling mode to check for correct charge Charge may need to be adjusted for cooling mode If adjustments are made in the cooling mode heating mod...

Страница 46: ...ser Air Source Heat Pump Sub Cooling 12 18 F Sub Cooling with Hot Gas Reheat 15 22 F Superheat 8 15 F Water Cooled Condenser Water Source Heat Pump Sub Cooling 4 8 F Sub Cooling with Hot Gas Reheat 4...

Страница 47: ...87 261 4 114 384 6 141 547 0 34 105 0 61 172 5 88 265 4 115 389 9 142 553 9 35 107 1 62 175 4 89 269 4 116 395 2 143 560 9 36 109 2 63 178 4 90 273 5 117 400 5 144 567 9 37 111 4 64 181 5 91 277 6 11...

Страница 48: ...charge See Startup section for information on air flow adjustment and refrigerant charge adjustment DX Cooling Set unit controls to cooling mode of operation with supply fans on Check the fans for cor...

Страница 49: ...an e coated coil and is required to maintain coating warranty coverage Coil cleaning shall be part of the unit s regularly scheduled maintenance procedures Failure to clean an e coated coil will void...

Страница 50: ...ended that a hose be used as a pressure washer will damage the fins The water to be used for the rinse is recommended to be of potable quality though a lesser quality of water may be used if a small a...

Страница 51: ...the restart time delay All settings and the last 4 faults are retained even if there is a complete loss of power DPM Setup Procedure With the supply voltage active to the module you can setup all of t...

Страница 52: ...Screen Vertical Format Default 2 sec Manual 2S 3S 4S 5S 6S 7S 8S 9S 10S 30S 1M 2M 3M 4M Phase Imbalance Percentage Screen Vertical Format Default 5 3 4 5 6 7 8 9 10 Fault Screen Vertical Format 0 most...

Страница 53: ...Table 11 45 70 tons Pre Filters Feature 6A Quantity Size Type 0 No Pre Filters A 18 20 x 20 x 2 Pleated 30 Eff MERV 8 Table 12 23 35 tons Unit Filters Feature 6B Quantity Size Type 0 9 20 x 20 x 2 Ple...

Страница 54: ...number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918 382 6400 Fax 918 382 6364 www aaon com Note Before calling technician shoul...

Страница 55: ...orrosion problems may occur especially when more factors are valued 0 Use is not recommended Water Containing Concentration mg l or ppm Time Limits Analyze Before AISI 316 SMO 254 Copper Alloy Nickel...

Страница 56: ...t 0 2 0 Manganese Mn 0 1 No Limit 0 1 0 Chloride Content Chloride Content Maximum Temperature 60 C 140 F 80 C 176 F 120 C 248 F 130 C 266 F 10 ppm SS 304 SS 304 SS 304 SS 316 25 ppm SS 304 SS 304 SS 3...

Страница 57: ...es No 2 Is the unit level Yes No 3 Are the unit clearances adequate for service and operation Yes No 4 Do all access doors open freely and are the handles operational Yes No 5 Have all shipping braces...

Страница 58: ...sure PSIG Suction Pressure PSIG 1 2 3 4 Refrigeration System 1 Cooling Mode Pressure Saturated Temperature Line Temperature Sub cooling Superheat Discharge N A N A Suction N A Liquid N A Refrigeration...

Страница 59: ...A Liquid N A Refrigeration System 2 Heating Mode Heat Pump Only Pressure Saturated Temperature Line Temperature Sub cooling Superheat Discharge N A N A Suction N A Liquid N A Refrigeration System 3 He...

Страница 60: ...o 2 Has the entire system been filled with fluid Yes No 3 Has air been bled from the heat exchangers and piping Yes No 4 Is the glycol the proper type and concentration N A if water Yes No 5 Is there...

Страница 61: ...cument any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper s...

Страница 62: ...adding the brazed plate heat exchanger cleaning instructions November 2012 Update of the IOM adding information about compressor cycling July 2013 Updated qualified installed warning and removed warr...

Страница 63: ...63...

Страница 64: ...Technical Support 918 382 6400 Note Before calling Technical Support please have the model and serial number of the unit available Parts For replacement parts please contact your local AAON Representa...

Отзывы: