98
Table 29 - 6-8 and 10 ton Gas Connections
Table 30 - 9, 11, 13, & 15 ton Gas
Connections
Model
Option
B2
Input
MBH
Connections
Quantity
Size
F
195.0
1
3/4” NPT
G
292.5
6
390.0
Table 31 - 14, 16-25 and 30 ton
Gas Connections
Table 32 - 26 and 31-70 ton
Gas Connections
*Obsolete
Table 33 - 55, 65 and 75-140 ton Gas
Connections
Model
Option
B2
Input
MBH
Connections
Quantity
Size
M
800
2
1” NPT
N
1600
2
1-1/2”
NPT
P
2400
After verifying gas inlet pressure and
manifold pressure the service technician shall
time the gas flow rate through the gas meter
with a stopwatch to verify the gas input rate.
Unit nameplate input rate value has been
calculated at the altitude where the unit was
shipped. Above 2,000 ft the input rate is
adjusted 4% for every 1,000 ft.
Figure 55 - RN Series Gas Heat Exchanger
Model
Option
B2
Input
MBH
Connections
Quantity
Size
2
90.0
1
1/2” NPT
K
150.0
L
210.0
3/4” NPT
Model
Option
B2
Input
MBH
Connections
Quantity
Size
4
270
1
3/4” NPT
8
405
1” NPT
C
540
Model
Option
B2
Input
MBH
Connections
Quantity
Size
*A
540
2
3/4” NPT
*B
780
C
540
1
1-1/2”
NPT
D
810
E
1080
Содержание RN Series
Страница 2: ......
Страница 32: ...32 Figure 5 RN Series 6 8 and 10 ton Unit Isolator Locations ...
Страница 33: ...33 Figure 6 RN Series 9 and 11 15 ton Unit Isolator Locations ...
Страница 34: ...34 Figure 7 RN Series 16 25 and 30 ton Unit Isolator Locations ...
Страница 35: ...35 Figure 8 RN Series 26 31 50 60 and 70 ton Unit Isolator Locations ...
Страница 36: ...36 Figure 9 Steel Mounting ...
Страница 102: ...102 Figure 56 Example 6 50 60 70 ton through the Base Gas Piping ...
Страница 105: ...105 Gas Heater Operating Instructions Figure 58 Gas Heater Instructions ...
Страница 129: ...Maintenance Log E Coated Coil ...