28
Model Option B2
Gas Heat
Electric Heat
Input Capacity
Output Capacity
Capacity
MBH
MBH
kW (208V)
kW (230V, 380V
460V, 575V)
1
=
Heat 1
60.0
48.0
7.5
10
2
=
Heat 2
90.0
72.0
15.0
20
3
=
Heat 3
100.0
80.0
22.5
30
4
=
Heat 4
270.0
218.7
30.0
40
5
=
Heat 5
140.0
112.0
37.5
50
6
=
Heat 6
390.0
315.9
45.1
60
7
=
Heat 7
160.0
128.0
60.1
80
8
=
Heat 8
405.0
328.1
75.1
100
9
=
Heat 9
90.1
120
A
=
Heat A
120.1
160
B
=
Heat B
150.2
200
C
=
Heat C
540.0
432.0
180.2
240
D
=
Heat D
810.0
648.0
210.3
280
E
=
Heat E
1080.0
864.0
240.3
320
F
=
Heat F
195.0
156.0
G
=
Heat G
292.5
234.0
K
=
Heat K
150.0
120.0
L
=
Heat L
210.0
168.0
M = Heat M
800.0
640.0
N = Heat N
1600.0
1280.0
P = Heat P
2400.0
1920.0
Wiring Diagrams
Unit specific wiring diagrams are laminated
and affixed inside the controls compartment
door.
Condensate Drain Pan
Unit requires drain traps to be connected to
the condensate drain pan of the unit. The 6-
25 and 30 ton units include one drain pan
connection and the 26 and 31-140 ton units
include two
drain pan connections.
Condensate drain pipes or p-traps for each
connection are factory supplied and shipped
loose in the controls compartment for field
installation.
If codes require a condensate drain line, the
line should be the same pipe size or larger
than the drain connection, include a p-trap,
and pitch downward toward drain. An air
break should be used with long runs of
condensate lines.
Unit should not be operated without a
p-trap. Failure to install a p-trap may
result in overflow of condensate
water.
CAUTION
Содержание RN Series
Страница 2: ......
Страница 32: ...32 Figure 5 RN Series 6 8 and 10 ton Unit Gasket Locations...
Страница 33: ...33 Figure 6 RN Series 9 and 11 15 ton Unit Gasket Locations...
Страница 34: ...34 Figure 7 RN Series 16 25 and 30 ton Unit Gasket Locations...
Страница 35: ...35 Figure 8 RN Series 26 31 50 60 and 70 ton Unit Gasket Locations...
Страница 42: ...42 Figure 19 Seismic Rigid Mount Curb...
Страница 71: ...71 12 Apply power to wheel and ensure that the wheel rotates freely without interference Belt Replacement...
Страница 80: ...80 Gas Heater Instructions Figure 43 Gas Heater Instructions...
Страница 113: ......
Страница 114: ......
Страница 115: ......