MiniLink PD 5 Technical Guide
7
CONFIGURATION
Figure 3: Baud Rate Setting
Network Loop & Local Loop Baud Rate Settings
Address Switches Show NET & LOOP
Set To ON for High Speed
Controller
Address Switch
NOTE:
The MiniLink PD 5 Is Factory Set
to Low Speed.
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
NET & LOOP Set To
High Speed
Network Loop & Local Loop Baud Rate Settings
MINILINK PD 5
NOTE:
The Power To The MiniLink Must
Be Removed And Reconnected In Order
For A Baud Rate Change To Take Effect.
*** The Local Loop (Switch 8) must be set to High Speed if it is connected to a loop
that ONLY includes VCB-X or VCC-X Controllers and/or any current or future
generation controllers set to high speed
****The Local Loop (Switch 8) must be set to Low Speed if it is being used on a
system that includes the VCM-X Controller, older generation Orion Controllers, or
any current controllers set to low speed.
115,200
ON
HIGH*
19,200
OFF
LOW**
57,600
ON
HIGH***
9600
OFF
LOW****
BAUD
Address Switches Show NET & LOOP
Set To OFF for Low Speed
Controller
Address Switch
1
2
4
8
16
32
SW2
OF
F
LOOP
NET
ON FOR
HI SPD
ADDRESS
NET & LOOP Set To
Low Speed
NETWORK
LOOP
SWITCH 7
BAUD
SPEED
SPEED
LOCAL
LOOP
SWITCH 8
* The Network Loop (Switch 7) must be set to High Speed if it is connected to a loop
that includes a CommLink 5 set to High Speed.
**The Network Loop (Switch 7) must be set to Low Speed if it is being used on a
system that includes a CommLink 5 set to Low Speed.