MiniLink PD 5 Technical Guide 

                                

 

11

APPENDIX B - MODULAR WIRING 

Power/Comm Board Wiring

Figure 7:  Power/Comm Board Wiring

A Power/Comm Cable Can Be Used

To Connect With The MiniLink PD

5’s Local Loop Connection Instead

Of Using 2-Conductor Twisted Pair

With Shield Cable. You Can Also

Use A Power/Comm Cable To

Connect With Another Power/Comm

Board, A System Manager Or A

VAV/Zone Controller.

Power/Comm Cable To Other Power/Comm Board(s),

System Manager, Or VAV/Zone Controllers On Local Loop Only.

If Desired, Instead Of Using A

Power/Comm Cable, You Can

Use 2-Conductor Twisted Pair

With Shield Cable To Connect

To The Power/Comm Board

From The Unit Controller,

MiniLink PD 5’s Local Loop

Connection, Or Another

Power/Comm Board.

Line Voltage

18-30 VAC

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Comm Loop Wiring Is

Straight Through

9600 or 57,600

Baud

Local Loop

RS-485

Local Loop RS-485

24 VAC Transformer (By Others)

4 Amp Slow Blow Fuse

WARNING!

DO NOT GROUND THE 24V TRANSFORMER
THAT IS TO BE USED WITH THE POWER/COMM
BOARDS. GROUNDING OF THE TRANSFORMER
WILL DAMAGE THE POWER/COMM BOARD
AND ALL BOARDS CONNECTED TO IT. A
SEPARATE TRANSFORMER MUST BE USED
FOR EACH POWER/COMM BOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER
DEVICES TO THE TRANSFORMER USED FOR
THE POWER/COMM BOARD!

NOTE:

Diagram Shown Is For

Wiring Of Power/Comm Board

When Used For Connecting Local

Loop Devices Such As VAV/Zone

Controllers, System Manager(s),

and Other Power/Comm Boards.

C

US

R

NOTE:

The MiniLink PD 5 will connect to a

Power/Comm Board Only If Power/Comm Cables

are Used to Daisy-Chain Between VAV/Zone

Controllers.

Содержание Orion Control Systems MiniLink PD 5

Страница 1: ...MiniLink PD 5 Technical Guide...

Страница 2: ...N Inc 2425 South Yukon Ave Tulsa OK 74107 2728 www aaon com Factory Technical Support Phone 918 382 6450 Controls Support Phone 866 918 1100 AAON P N G042660 Rev 01C Copyright October 2020 AAON Inc AA...

Страница 3: ...etting 6 Network Loop Local Loop Baud Rate Selection 7 APPENDIX A TERMINAL WIRING 8 MiniLink PD 5 Terminal Wiring 8 Networked Single Loop Wiring with VAV Zone BACnet 9 Networked Multiple Loop Wiring w...

Страница 4: ...nication loops into an RS 485 network communications system See Figure 1 page 5 for dimensions The MiniLink PD 5 is required on the Orion Control system to separate local loops Up to 60 MiniLink loops...

Страница 5: ...2 07 4 1 5 96 0 66 2 73 0 29 1 2 4 8 16 32 SW2 OFF LOOP NET ON FOR HI SPD ADDRESS Environmental Requirements The MiniLink PD 5 needs to be installed in an environment that can maintain a temperature r...

Страница 6: ...Any Changes To Take Effect 1 2 4 8 16 32 SW2 OFF LOOP NET ON FOR HI SPD ADDRESS Address Dipswitch Setting MINILINK PD 5 16 32 NET LOOP 8 4 2 1 Address Switch Shown Is Set For Address 1 Address Switch...

Страница 7: ...includes VCB X or VCC X Controllers and or any current or future generation controllers set to high speed The Local Loop Switch 8 must be set to Low Speed if it is being used on a system that includes...

Страница 8: ...ends Using A Separate Transformer For Each Device In Order To Eliminate The Potential For Damaging Devices Due To Incorrect Polarity CAUTION Disconnect All Communication Loop Wiring From The MiniLink...

Страница 9: ...gure The Controllers Line Voltage System Manager TS L Back View 18 30 VAC 6 VA R S T BLACK R Connect To T SH R Terminals On HVAC Unit Controller RED 18 30 VAC BROWN GND WHITE T BARE S 1uF YS102178 R4...

Страница 10: ...STAT2 SW2 TB1 TB2 U8 U10 U12 D4 J6 J7 J8 R43 R44 R46 C33 OFF T SH R 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1uF 1uF 1uF 1uF 1002 1002 T SH R...

Страница 11: ...ion Or Another Power Comm Board Line Voltage 18 30 VAC R SH T R SH T R SH T R SH T All Comm Loop Wiring Is Straight Through 9600 or 57 600 Baud Local Loop RS 485 Local Loop RS 485 24 VAC Transformer B...

Страница 12: ...Severe Damage To The Devices May Result AAON Recommends Using A Separate Transformer For Each Device In Order To Eliminate The Potential For Damaging Devices Due To Incorrect Polarity CAUTION Disconne...

Страница 13: ...Back View of CommLink 5 Front View of CommLink 5 Note Either A Modular System Manager SD Modular Service Tool SD Or PC With Prism 2 Software Installed Can Be Used To Program And Configure The Orion S...

Страница 14: ...tober 2020 AAON All Rights Reserved AAON Factory Technical Support 918 382 6450 techsupport aaon com AAON Controls Support 866 918 1100 Monday through Friday 7 00 AM to 5 00 PM Central Standard Time N...

Отзывы: