           MiniLink PD 5 Technical Guide

 

4

OVERVIEW

Overview & Features

Features

The 

MiniLink PD 5

 utilizes token passing communication ar-

chitecture. The 

MiniLink PD 5

 is designed to serve as the local 

communications loop master. This means that it is responsible 

for sending the token to all the controllers on the local commu-

nications loop. 

Network communications are RS-485 type operating at 19,200 or 

115,200 baud. Local communications are also RS-485 type and 

operate at 9600 or 57,600 baud. See 

Figure 2, page 6.

The MiniLink PD 5 is factory default set to low speed. The baud 

rate is set with dipswitches 7 & 8. See 

Figure 3

,

 page 7

.

Overview

The MiniLink PD 5 is an RS-485 communications device that 

is used to integrate multiple local RS-485 communication loops 

into an RS-485 network communications system. See 

Figure 1

,

 

page 5

 for dimensions.

The MiniLink PD 5 is required on the Orion Control system to 

separate local loops. Up to 60 MiniLink loops can be on a system.

Local loop terminals of the MiniLink PD 5 are designed to con-

nect to controllers that are daisy-chained together on its RS-485 

local communications loop. 

Network RS-485 loop terminals on the MiniLink PD 5 are used 

to daisy-chain multiple MiniLinks back to a CommLink 5 to 

form a network communications loop. This provides for a fully 

networked RS-485 communications system. 

The MiniLink PD 5 is required for VAV systems to allow infor-

mation to be shared between the HVAC Unit Controller and the 

VAV/Zone BACnet

®

 

Controllers (VAVZB). 

It is also 

required 

for zoning systems to facilitate voting of the zones to determine 

the HVAC units heating and cooling mode of operation. It also 

provides tenant-logging capabilities.  

Содержание Orion Control Systems MiniLink PD 5

Страница 1: ...MiniLink PD 5 Technical Guide...

Страница 2: ...N Inc 2425 South Yukon Ave Tulsa OK 74107 2728 www aaon com Factory Technical Support Phone 918 382 6450 Controls Support Phone 866 918 1100 AAON P N G042660 Rev 01C Copyright October 2020 AAON Inc AA...

Страница 3: ...etting 6 Network Loop Local Loop Baud Rate Selection 7 APPENDIX A TERMINAL WIRING 8 MiniLink PD 5 Terminal Wiring 8 Networked Single Loop Wiring with VAV Zone BACnet 9 Networked Multiple Loop Wiring w...

Страница 4: ...nication loops into an RS 485 network communications system See Figure 1 page 5 for dimensions The MiniLink PD 5 is required on the Orion Control system to separate local loops Up to 60 MiniLink loops...

Страница 5: ...2 07 4 1 5 96 0 66 2 73 0 29 1 2 4 8 16 32 SW2 OFF LOOP NET ON FOR HI SPD ADDRESS Environmental Requirements The MiniLink PD 5 needs to be installed in an environment that can maintain a temperature r...

Страница 6: ...Any Changes To Take Effect 1 2 4 8 16 32 SW2 OFF LOOP NET ON FOR HI SPD ADDRESS Address Dipswitch Setting MINILINK PD 5 16 32 NET LOOP 8 4 2 1 Address Switch Shown Is Set For Address 1 Address Switch...

Страница 7: ...includes VCB X or VCC X Controllers and or any current or future generation controllers set to high speed The Local Loop Switch 8 must be set to Low Speed if it is being used on a system that includes...

Страница 8: ...ends Using A Separate Transformer For Each Device In Order To Eliminate The Potential For Damaging Devices Due To Incorrect Polarity CAUTION Disconnect All Communication Loop Wiring From The MiniLink...

Страница 9: ...gure The Controllers Line Voltage System Manager TS L Back View 18 30 VAC 6 VA R S T BLACK R Connect To T SH R Terminals On HVAC Unit Controller RED 18 30 VAC BROWN GND WHITE T BARE S 1uF YS102178 R4...

Страница 10: ...STAT2 SW2 TB1 TB2 U8 U10 U12 D4 J6 J7 J8 R43 R44 R46 C33 OFF T SH R 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1uF 1uF 1uF 1uF 1002 1002 T SH R...

Страница 11: ...ion Or Another Power Comm Board Line Voltage 18 30 VAC R SH T R SH T R SH T R SH T All Comm Loop Wiring Is Straight Through 9600 or 57 600 Baud Local Loop RS 485 Local Loop RS 485 24 VAC Transformer B...

Страница 12: ...Severe Damage To The Devices May Result AAON Recommends Using A Separate Transformer For Each Device In Order To Eliminate The Potential For Damaging Devices Due To Incorrect Polarity CAUTION Disconne...

Страница 13: ...Back View of CommLink 5 Front View of CommLink 5 Note Either A Modular System Manager SD Modular Service Tool SD Or PC With Prism 2 Software Installed Can Be Used To Program And Configure The Orion S...

Страница 14: ...tober 2020 AAON All Rights Reserved AAON Factory Technical Support 918 382 6450 techsupport aaon com AAON Controls Support 866 918 1100 Monday through Friday 7 00 AM to 5 00 PM Central Standard Time N...

Отзывы: