           MiniLink PD 5 Technical Guide

 

12

APPENDIX B - MODULAR WIRING

MiniLink PD 5 Modular Wiring 

Figure 8:  MiniLink PD 5 Modular Wiring  

GND

18-30 

V

AC

CAUTION:

Disconnect All Communication Loop Wiring

From The MiniLink Before Removing Power

From The Controller. Reconnect Power And

Then Reconnect Communication Loop Wiring.

24 VAC Transformer

Size For 6 VA Max. Load

Some Installers Like To Use One Large 24 VAC Transformer
To Power Several Devices. This Is Allowable As Long As
Polarity Is Maintained To Each Device On The Transformer
Circuit.

Using Separate Transformers Also Allows Redundancy In
Case Of A Transformer Failure. Instead Of Having 8 Devices
Inoperative Because Of A Malfunctioning Transformer, You
Have Only 1 Device Off Line.

WARNING: If Polarity Is Not Maintained, Severe Damage
To The Devices May Result. AAON Recommends
Using A Separate Transformer For Each Device In Order
To Eliminate The Potential For Damaging Devices Due To
Incorrect Polarity.

CAUTION:

Disconnect All Communication Loop Wiring

From The MiniLink Before Removing Power

From The Controller. Reconnect Power And

Then Reconnect Communication Loop Wiring.

MINILINK PD 5

P

D
DR

V

LOOP

DR

V

NET DRV

PIC32 MLPD

YS102398 REV 3

NETWORK

LOCAL

PD COMM

POWER

COMM

ML

PD

MADE IN USA

SERIA

L
#

C22

C23

C30

C37

C40

J1

J3

R1

R2

R3

R4

R20

R21

R
2

2

R23

R24

R
2

5

R26

R27

R31

PDSTAT1

PDSTAT2

TB1

TB2

U8

U10

U
1

2

D4

J6

J7

J8

R43

R44

R46

C
3

3

T

SH

R

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

.1

u

F

.1uF

.1uF

.1uF

1

0

0

2

1

0

0

2

T

SH

R

C24

COMM

1

2

4

8

16

32

SW2

OFF

LOOP

NET

ON FOR

HI SPD

ADDRESS

Connect Local Loop Comm

Cable To Power/Comm

Board (If Used).

On Multiple Loop Systems, Connect

Modular Cable To Next MiniLink’s

Network Comm Connector.

Содержание Orion Control Systems MiniLink PD 5

Страница 1: ...MiniLink PD 5 Technical Guide...

Страница 2: ...N Inc 2425 South Yukon Ave Tulsa OK 74107 2728 www aaon com Factory Technical Support Phone 918 382 6450 Controls Support Phone 866 918 1100 AAON P N G042660 Rev 01C Copyright October 2020 AAON Inc AA...

Страница 3: ...etting 6 Network Loop Local Loop Baud Rate Selection 7 APPENDIX A TERMINAL WIRING 8 MiniLink PD 5 Terminal Wiring 8 Networked Single Loop Wiring with VAV Zone BACnet 9 Networked Multiple Loop Wiring w...

Страница 4: ...nication loops into an RS 485 network communications system See Figure 1 page 5 for dimensions The MiniLink PD 5 is required on the Orion Control system to separate local loops Up to 60 MiniLink loops...

Страница 5: ...2 07 4 1 5 96 0 66 2 73 0 29 1 2 4 8 16 32 SW2 OFF LOOP NET ON FOR HI SPD ADDRESS Environmental Requirements The MiniLink PD 5 needs to be installed in an environment that can maintain a temperature r...

Страница 6: ...Any Changes To Take Effect 1 2 4 8 16 32 SW2 OFF LOOP NET ON FOR HI SPD ADDRESS Address Dipswitch Setting MINILINK PD 5 16 32 NET LOOP 8 4 2 1 Address Switch Shown Is Set For Address 1 Address Switch...

Страница 7: ...includes VCB X or VCC X Controllers and or any current or future generation controllers set to high speed The Local Loop Switch 8 must be set to Low Speed if it is being used on a system that includes...

Страница 8: ...ends Using A Separate Transformer For Each Device In Order To Eliminate The Potential For Damaging Devices Due To Incorrect Polarity CAUTION Disconnect All Communication Loop Wiring From The MiniLink...

Страница 9: ...gure The Controllers Line Voltage System Manager TS L Back View 18 30 VAC 6 VA R S T BLACK R Connect To T SH R Terminals On HVAC Unit Controller RED 18 30 VAC BROWN GND WHITE T BARE S 1uF YS102178 R4...

Страница 10: ...STAT2 SW2 TB1 TB2 U8 U10 U12 D4 J6 J7 J8 R43 R44 R46 C33 OFF T SH R 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1002 1uF 1uF 1uF 1uF 1002 1002 T SH R...

Страница 11: ...ion Or Another Power Comm Board Line Voltage 18 30 VAC R SH T R SH T R SH T R SH T All Comm Loop Wiring Is Straight Through 9600 or 57 600 Baud Local Loop RS 485 Local Loop RS 485 24 VAC Transformer B...

Страница 12: ...Severe Damage To The Devices May Result AAON Recommends Using A Separate Transformer For Each Device In Order To Eliminate The Potential For Damaging Devices Due To Incorrect Polarity CAUTION Disconne...

Страница 13: ...Back View of CommLink 5 Front View of CommLink 5 Note Either A Modular System Manager SD Modular Service Tool SD Or PC With Prism 2 Software Installed Can Be Used To Program And Configure The Orion S...

Страница 14: ...tober 2020 AAON All Rights Reserved AAON Factory Technical Support 918 382 6450 techsupport aaon com AAON Controls Support 866 918 1100 Monday through Friday 7 00 AM to 5 00 PM Central Standard Time N...

Отзывы: