10
Connections
■
How to connect
Single connection
Multi drop connection
Item
Description
Accessory
①
RS-485 connector
(power clamp wire mount socket)
Model: AX-35505-6200-A
(Made by 3M 35505-6200-A00)
○
(
1 piece
)
②
RS-485 cable
Recommended specification
・
Twisted pair cable with shield
・
Wire conductor size AWG#20
(
0.50mm
2
)
・
Characteristic impedance
100
Ω
×
③
Branching connector
Model: AX-35715-A (Made by 3M 35715-L010-A00)
*
For multi drop connection.
RS-485 connector (power clamp wire mount socket) also needs to
be purchased additionally.
×
■
Connecting method of cable and connector
①
Connect the two signal lines (DATA+, DATA-) in twisted pairs
and wire the shield of RS-485 to the SLD terminal.
If the host device does not have a signal ground, the SG terminal
connecting is not necessary.
②
Insert the lead wire all the way in to the cover (yellow portion) without
peeling off the cover of the lead wire.
③
Push the cover into the body and fix it.
④
Make sure that the cover is level with the body and that there is no gap
between the body and the cover.
②
RS-485 cable
①
RS-485 connector (power clamp wire mount socket)
③
Branching connector
Cover (yellow part)
Before cable crimping
Body (black part)
After cable crimping