7. Switch
・
Set the parameters required for communication using the AD-8551R switches (SW-1 to 5).
Caution
・
If the setting is changed, be sure to turn on the power off and on again of AD-8551R. When the power is turned on,
the switch status is read and applied to operations
How to operate the switch
SW-1 to 3, 5
When lever No.1 is moved to the “ON” side, “1” Is set.
SW-4
Turn the center arrow to set.
It can be set from 0 to F.
Factory setting
The switch status and settings at the factory setting are as follows. Refer to “7-3. RS-485 function settings” “7-4.
RS-232C function settings” for the settings that need to be changed.
SW-1 SW-2 SW-3 SW-4 SW-5
Item
Factory setting
value
Switch status at factory setting
RS-485 baud rate
9600
SW-1 No1
:
0
SW-1 No2
:
0
RS-485 parity
EVEN
SW-1 No3
:
0
SW-1 No4
:
0
RS-232C baud rate
2400
SW-2 No1
:
0
SW-2 No2
:
0
RS-485 communication method
Mosbus RTU mode SW-2 No3
:
0
Device address
01
SW-3 No3
:
0
SW-3 No4
:
0
SW-4
:
1
Terminating resistor
None
SW-5 No1
:
0
Fixed decimal point function
AUTO
SW-5 No2
:
1
SW-5 No3
:
1
SW-5 No4
:
1
“1”
“0”
No. 1 on the left and No. 4 on the right.
Lever
1
1
1
0
0 0
0 0
0 0
0
1
0
0
0
0
0