4.2.6 Fault and Alarm Display
Fault and alarm display rules.
1
)
Display fault code when fault and alarm exist at the same time.
2
)
When there is no fault but there are several alarms, the alarm codes will be displayed
cyclically.
3
)
Display current parameters when there is no fault or alarm.
For fault codes and alarm codes of the FT50 series frequency converter, please refer to the
Chapter 7. The fault and alarm display description is as follows.
Table 4-5 Fault and alarm display d
escription
State
Display
Description
When an
alarm occurs
When an alarm occurs, the frequency converter
can operate normally, and the last two digits
display the alarm code (the figure on the left
shows an example, alarm No.1 )
When a fault
occurs
When a fault occurs, the frequency converter is
in the stopped state, and the last two digits
display the fault code (the figure on the left
shows an example, fault No.1 )
4.2.7 Keyboard Password Lock Function
This function is used to lock the keyboard to prevent the keyboard from being operated by
unauthorized personnel or the parameters are set incorrectly. When the password is set, the
user must enter the correct password before setting the parameters, otherwise the user can
only check the parameters.
1) Set initial password for keypad lock
When using this function for the first time, the user sets the value of parameter P3346.F as the
keyboard lock password. The user must remember the password when setting the keyboard
lock password, otherwise the operation panel cannot be unlocked easily.
2) Keyboard lock settings
If the user needs to lock the keyboard after setting the password, the user can press the
MENU/BACK+ ENTER key combination or set the parameter value to 0. If the password has
been set, the user needs to enter the correct password each time the keyboard is locked or
power on again before setting the parameters. If the password is correct, the password can be
modified by entering the new password.
NOTICE
When the user forgets the set keyboard lock password and cannot unlock the
operation panel, please contact the A-TS technology for technical support.