waits for a heat request (determined by the Thermostat or 

controlling probe inputs). All outputs are off in this state 

except that if the Post-Circulate time is set to continuous, 

the pump will be on. When the heat request is received, 

the system moves to the Pre-Circulate state.

•  Pre-Circulate:

  The yellow lED is turned off and the green “Running” lED is 

turned on. The green lED will remain on for all other states 

except the fault states.  Cold purging clears out any combustion 

gas that may be in the combustion chamber. When purging is 

complete the system moves to the Heat State.

•  Heat Stage

  The system will command the FCB micros to start their heat 

sequence.  will be activated in order based on an algorithm 

that determines how much heat is needed. The system will 

remain in this state until the heat request is satisfied, the 

Tstat is opened, or a fault occurs.

•  Soft Fault State: (See “Fault Description” section for list of 

soft and Auto Reset faults.)

  The pump remains on for the selected post-circulate 

time to cycle the hot water out of the boiler. The FCB is 

commanded to shut down and the Alarm output is turned 

on. The green lED turns off and the red “Service” turns 

on. The MCB remains in this state until one of the following 

occurs:

 

•  One hour passes (automatic restart after one hour)

 

•  If Communications error system will automatically    

restart if communications re-establishes.

 

•  If user presses Select key while current error screen is 

displayed (Hard reset).

 

•  If high-limit error - the outlet temperature drops below 

the high limit trip point minus the high limit differential. 

(outlet water temperature drops to safe level). The fault 

is logged in the error history when the fault  state is 

exited.

 

•  Hard Fault State: (See “Fault Description” section for 

list of soft and Auto Reset faults.)  The pump remains 

on for the selected post-circulate time to cycle the hot 

water out of the boiler. The FCB is commanded to shut 

down and the Alarm output is turned on.  The green 

lED turns off and the red “Service” turns on and off 

(flashes). The only way to exit this state is for the user 

to press the Select key while the current error screen is 

displayed. The fault is logged in the error history when 

the fault state is exited.

While the MCB is in the Heating mode the FCB moves from 

Idle, to Pre-Purge, to Heat Igniter, to Check for Flame, and 

then to Heating. The process waits in this state until the call 

for heat is satisfied, the thermostat input is opened, or a fault 

occurs.  When heat is satisfied, the sequence continues to 

Post-Purge and then back to Idle.  If three tries for ignition has 

been selected on the MCB dipswitch and flame is not detected 

at the appropriate time, then the sequence moves to the Inter-

Purge state for 15 seconds and the FCB heat sequence is 

repeated. If flame is still not detected after the third try the 

process declares a fault, jumps out of sequence and goes to 

the error state. other types of faults detected at any time will 

also cause a jump to the error state.

Description of FCB control states:

•  Idle State:

  When any error is declared during idle state-The system will 

remain in this state until the MCB request a heating cycle, 

or a cold purge.

•  Pre-Purge State:

  The blower is turned on.  After 10 to 34 seconds (34 

seconds for cold purging) the system switches to the Heat 

Igniter State.  

•  Heat Igniter State:

  The sequence of operation is as follows: “The igniter relay is 

energized and the heat up period begins. After 18-20 seconds, 

if the igniter has reached a minimum of 2.8 amps, the gas valve 

safety circuit is then activated. If in this amount of time, the igniter 

fails to reach a minimum amp draw of 2.8 amps, the unit will 

re-cycle up to 3 times before locking out on igniter hardware 

failure. If the igniter does reach the minimum required amp draw 

of 2.8 amps, the gas valve circuit is energized, and the system 

advances to Flame Check status.

•  Check for Flame State:

  The gas valve is turned on. After 1.5 seconds, the system 

checks that the gas valve relay is on.  If it is not, the ignition 

trial is considered to have failed and the system advances to 

the Inter-Purge state, if any ignition trials remain, otherwise an 

error is declared.

  The flame sensor is checked.  If flame is detected, the igniter 

is turned off.  The state machine then advances to the Heating 

State.  If after 5 seconds, the flame is still not sensed then the 

ignition trial is considered to have failed.  The state machine 

advances to Inter-Purge if any ignition trials remain, otherwise 

an error is declared.

•  Heating State:

  The system remains in this state until the call for heat is 

cancelled or a fault occurs.  The system returns to the Idle state 

if the call for heat is cancelled, or satisfied and to the appropriate 

fault state if a fault occurs. 

•  Inter-Purge State:

  The gas valve and the igniter are turned off.  The blower is on.  

After approximately 15 seconds the system goes back to the 

Heating Igniter State.

•  Post-Purge State

  The gas valve and the igniter are turned off. The blower 

is then left on for approximately 25 seconds, the system 

returns to the Idle state.

•  Error State

  The gas valve and the igniter are turned off. The FCB micro tells 

the MCB micro which error has occurred. The system waits in 

this state until the MCB sends a command to clear the error, 

and the system returns to the idle state.

•  Cold Purge State

  Cold purge occurs when the MCB micro commands the blower 

to go on before lighting to clear the unit of residual gases. 

This state normally lasts approximately 32 seconds but on a 

special situation can last up to 5 minutes. If on the first call for 

heat after power up, blower prover switch is open, this state 

will take up to 5 minutes before declaring an error.

  The MCB will wait the normal cold purge time (normally 32 

seconds) before checking for activation of all active blower 

prover.  If blower prover is active at this time the MCB cancels 

the cold purge request.  After the first cold purge has been done 

a flag is set to prevent further activation of the shutter adjust 5 

minute delay.  Any further requests for cold purge will last the 

normal cold purge time. The FCB will go into fault mode  if the 

Содержание VF VB 500

Страница 1: ...e any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installati...

Страница 2: ...nces known to the State of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical...

Страница 3: ...3 GENERAL SAFETY...

Страница 4: ...trol assembly pro vided on the boiler met safe lighting and other performance criteria Detailed installation diagrams are found in this manual These diagrams will serve to provide the installer a refe...

Страница 5: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The st...

Страница 6: ...6 CONNECTION DIAGRAM...

Страница 7: ...7...

Страница 8: ...8 Figure 1 SCHEMATIC DIAGRAM VB VW 500 750 1000 SCHEMATIC DIAGRAM...

Страница 9: ...9 LIGHTING OPERATION INSTRUCTIONS FOR MODELS VB VW 500 750 AND 1000...

Страница 10: ...stem or something similar Through this connection multiple boilers can also be linked together CAUTION The internal communications cables should never be connected to the external communications conne...

Страница 11: ...me rod is missing or shorted the flame will not be detected OUTPUTS FROM MCB Relay Contact Output Alarm MCB 24VAC optional Provides electrical power to operate an external alarm This can be an audio d...

Страница 12: ...u activated screens Within each of the screens helpful information can be displayed by pressing the Help button The LED s visually inform the user about the mode the system is in The touch switches al...

Страница 13: ...jump to the error state Description of FCB control states Idle State When any error is declared during idle state The system will remain in this state until the MCB request a heating cycle or a cold...

Страница 14: ...to change the automatically resettable High Limit Setpoint 1 Press the MENU key 2 Scrollthe withtheDOWNkeynexttoUSERSETTINGSCREEN 3 Press the SELECT key 4 Scroll the with the DOWN key until it is poin...

Страница 15: ...rds in screens to reach a desired item and to change setpoints and user settings They have an auto increment decrement feature for some of the configurations and values When you first press one of the...

Страница 16: ...ected wiring Note The MRHL can be checked by disconnecting the outlet probe from the MCB and reading the resistance across the two active pins on the connectorattheendoftheprobecable Thevalueshouldbea...

Страница 17: ...Give reasonably quiet operation during initial ignition operation and extinction Cause no excessive lifting of flame from burner ports If the preceding burner characteristics are not evident check fo...

Страница 18: ...ible shortened service life BURNER MAINTENANCE Qualified servicers should follow this procedure when the boiler s burner needs cleaning 1 Turn off the electrical power to the boiler and close the main...

Страница 19: ...solidsexist Asthewaterisheated these tendtodropoutdepositingasscaleorlime Thisscalemustberemoved before the heat exchanger tubes become blocked DELIMING The amount of calcium carbonate lime released f...

Страница 20: ...20 notes...

Страница 21: ...21 notes...

Страница 22: ...22 notes...

Страница 23: ...ation for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts so the above limitation may not apply to you 5 CLAIM PROCEDURE Any cla...

Страница 24: ...24 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Отзывы: